www.enviromaster.com

CAC Cassette Evaporator

16

REFRIGERANT PROCESSING

Finish all pipe connecting before

proceeding to charging the system.

Follow the instructions in the outdoor

unit for line evacuation, opening service

valves, and fi nal charge adjustments. Op-

eration charts and charge tables can be

found in the EMI Condenser IOMs.

WARNING!

It is illegal to discharge

refrigerant into the atmosphere.

Use proper reclaiming methods

and equipment when installing

or servicing this unit.

1. Clean the ends of tubing and insert into

fi ttings.

2. Protect the valves by wrapping with a

wet rag "heat sink" before brazing.

3. We recommend the use of a shield (can

be made from some scrap metal) to

protect the paint.

4. Braze tubing into fi ttings.

5. Attach manifold set.

Refer to Charts in condenser manual to

“fi ne tune” the refrigerant charge.

Heat sink

Shield

S1C

Shown

Manifold

Vaccum Pump

Micron Gage

S1C

Shown

6. Evacuate line to 500 microns or less to

ensure all moisture has been removed

and there are no leaks.

7. Once certain of a good evacuation and

leak free joints, back-seat the valves

(counter-clockwise) to open and allow fac-

tory charge to fi ll lines and indoor unit.