CAC CASSETTE EVAPORATOR INSTALLATION INSTRUCTIONS

1. Route the cable through the appropriate

hole in the control box for the High Volt

electrical wiring.

High Volt Electrical Wiring

2. Secure the cable.

3. Refer to the wiring diagram (see below)

to connect the ground wire to the ground

lug.

High Volt Electric Cable

Low Volt Electrical

Connections

4. Then refer to the wiring diagram to

connect the power wire to (L1) and the

other wire to (L2) at the power connector

location (terminal block).

(L1)

(L2)

Low Volt Interconnect Wiring

Refer to the wiring diagram to connect the low Volt wiring to

the appropriate terminals. The wiring diagram located

on the inside of the con-

trol box cover.

Once the connections are

made replace control box

cover with the wiring diagram

facing in and secure with the

four screws.

Low Volt

Connections

Wiring Diagram

The 24V control transformer is located in the air handler unit. This

provides low Volt control power to both the air handler and condenser.

Depending on the models selected, the low Volt interconnect control

wiring may be different.

NOTE: All low Volt interconnect

wiring must be at least 18 awg.

Ground Wire

Ground Lug