www.enviromaster.com

CAC Cassette Evaporator

22

Low Volt Controls

TROUBLESHOOTING PROCEDURE

Continued

Cooling Only Units:

Cooling only units require 18awg low Volt

interconnecting wires between the indoor

unit, outdoor units and thermostat. Ter-

minals designated “Y1” (yellow) and “C”

(brown) of the indoor air handler should

be connected to the corresponding “Y”

(yellow) and “C” (brown) wires or termi-

nals of the outdoor condenser. Other

wire(s) or terminals such as “R” (red) may

not be needed and should be protect from

making contact with the junction box or

other metal surfaces.

Terminals “R”, “Y, “G”, “W” and “C” need

to connect to the indoor, wall mounted

thermostat.

NOTE: “W” is required for units with

electric heat only “C” may not be

needed on some thermostats.

Refer to low Volt interconnect diagram

interconnect diagram figure 1 for remote

thermostat connection.

A 24V transformer located in the indoor

air handler unit provides low Volt control

power to both the indoor air handler and

outdoor condenser. The 24v-power sup-

ply can be measured by placing a meter

across the “R” and “C” low Volt termi-

nals of the air handler. The remote wall

mounted thermostat will switch on and off

the condenser through the yellow (Y) and

black (Y1) wires. When the thermostat is

calling for cooling, 24V can be measured

between terminals (wires) Y and C.

The indoor unit contains an electronic anti

short cycle timer feature (ASCT) that will

prevent the outdoor condenser from short

cycling. After the thermostat is satisfied

there will be a three minute delay before

the condenser is allowed to re-start.

Electric Heat:

Units with electric heat utilize a control

relay located on the circuit board in the

control box. As a safety feature, an auto

resetting limit switch located on the heat-

er assembly will interrupt power to the

heater should an over-temperature condi-

tion occur. Each electric heat assembly is

also equipped with a one time fuse link.

Should electric heat temperatures rise

above the auto resetting limit switch, a

non-resetting, one time fuse link will open

and the heater will remain off. If this oc-

curs the limit switch assembly must be re-

placed. Contact EMI technical service for

a replacement.

The following current values apply when

the unit is connected to a 230V power

supply. These values include fan motor

current. If the supply power is different,

this will in turn affect the amp draw of the

heater.

5kw = 22.3 amps,

3kw = 13.5 amps,

1.5kw = 6.9 amps.

Units with Condensation Pumps:

EMI CAC is equipped with an internal

condensate pump capable of removing

condensate up to a three foot vertical lift.

Condensation generated by the evapo-

rator will collect in the pumps’ reservoir.

When the water level is high enough, a

float switch will close and energize the

pump motor clearing the water from the

reservoir. Should, for any reason, the wa-

ter exceed the maximum preset level, a

safety switch will open, there by interrupt-

ing the (Y1) signal to the condenser. This

will prevent the evaporator from generat-

ing additional condensation and spilling

out of the unit.