EMI CAC User Manual

Page 9

Advertising
background image

www.enviromaster.com

9

CAC Cassette Evaporator

Fresh Air

Knockout

Branch Duct Knockout

Small Unit

Medium &

Large Units

Notes: The number of knock-outs var-

ies depending on unit size.

• Branch duct knock-outs are 5¼” round

• Fresh air knock-outs are 1¼” x 2½”

rectangular on 12k, and 3” square on

24-36k

Recommendation: No more then

10’ of branch duct or fresh air duct

should be installed.

CONDENSATE PIPING

The unit can now be piped up in accor-

dance with good refrigeration and/or

plumbing practices.

The Cassette is supplied with a 1/2”

I.D. fl exible PVC hose for connection to

copper or plastic drain pipework. When

installing the Cassette the following points

should be remembered:
1. Maximum pump lift is 36”.
2. The highest point in the condensate

pipework should be as close to the

unit as possible. This prevents a large

volume of water draining back into the

unit when it is switched off.

NOTE: There is a check valve at the

pump discharge to prevent water

from draining back into the unit. This

piping technique will minimize any is-

sues should the check valve become

stuck open from airborne debris.

Correct

Incorrect

Condensate Drain Connection

3. Condensate pipework should slope

downwards in the direction of water

fl ow with a minimum gradient of (1”

per 10’). There must not be any uphill

gradients other than in the fi rst 36” of

pipework from the Cassette.

4. When multiple Cassettes are connect-

ed to a common condensate drain,

ensure the drain is large enough to

handle the volume of condensate

from several Cassettes. It is also rec-

ommended to have an air vent in the

condensate pipe work to prevent any

air locks.

Duct collars: Branch duct and fresh air

duct collars can be attached to the Cas-

sette chassis by following the steps below:

1. Locating the knock-out holes.

Advertising