EMI CAC User Manual

Page 23

Advertising
background image

www.enviromaster.com

23

CAC Cassette Evaporator

TROUBLESHOOTING PROCEDURE

Continued

Frequently Asked Questions

Q: The system has just been installed using

an EMI indoor unit and a non-EMI con-

denser and the unit will not operate.

A: The CAC air handlers is manufactured

with a low Volt transformer installed.

EMI outdoor condensers are manufac-

tured without a low Volt transformer.

When connecting an EMI evaporator to

a non-EMI condenser, check to ensure

that there is a 24V control transformer

in either in the indoor unit or outdoor

unit. Only one transformer is required.

If both the indoor unit and outdoor unit

contain a transformer, one must be re-

mover from the system.

Q: The condenser will not start although

the indoor unit appears normal. What

should I do?

A: At the indoor thermostat, make sure

that the control is in cooling and the

setpoint temperature is below room

temperature. Next, using a Volt meter,

check for 24V across the yellow (Y)

and brown (C) wires. If 24V is present

then check for wiring breaks or improp-

er connections between the indoor and

outdoor units.

A: Some EMI condensers are equipped

with a manual reset high-pressure

switch. It is located on the high side of

the system usually on the discharge

line of the compressor. To reset, sim-

ply push the red button in. If the switch

was tripped there will be a “click” when

it resets.

A: CAC air handlers are equipped with an

internal condensate pump with a high

level safety switch. If the condensate

reaches a critical level or if power is

lost to the indoor unit, the safety cir-

cuit will open and low Volt power to the

condenser (terminal “Y1”) will be re-

moved. The condensate pump should

be checked for obstruction. The con-

densate pump assembly can be re-

moved through the side access panel.

After removal, inspect the drain pan

to determine if the condensate is not

being removed properly from the unit.

Inspect all drain lines to ensure there

is no blockage preventing condensate

removal.

Q: How long will the fan run?

A: While the unit is in cooling or heating

and auto fan mode is selected, the

fan will cycle with the call for cooling

or heating. When the room tempera-

ture reaches setpoint temperature the

heat/cool call is dropped. The fan will

then stay on for an additional 60 sec.

to purge unit of any residual energy.

Q: What causes my indoor unit to freeze-up?

A: Evaporator freeze up is usually the

symptom of another problem. CAC air

handler units are equipped with freeze

protection to prevent freeze up from

occurring. If freeze up does occur then

check the following.

• Check that the freeze sensor inserted

fully and snug in the coil fin. If not an-

other location may need to be select-

ed. Be careful not to insert the sensor

directly into the coil tube rather insert

the sensor between two tubes.

• Check the indoor air filter. It should

be clean and free of dirt. A dirty filter

will reduce airflow and efficiency. Also

check that the coil is clean. If the coil

is dirty then it should be cleaned us-

ing an appropriate coil cleaner or mild

detergent.

Advertising