EMI CAC User Manual

Page 6

Advertising
background image

www.enviromaster.com

CAC Cassette Evaporator

6

CAC CASSETTE PREPARATION AND POSITIONING

POSITIONING

The Cassette installation position should be

selected with the following points in mind:

1. Pipe work, electrical connections, con-

trol box and condensate pump access

panels should be readily accessible.

2. The unit should be positioned at least

5 ft. from a wall or similar obstruction.

Position the unit as close to the center

of the room as possible to insure air is

distributed evenly.

3. Position the unit so that the discharge air

does not blow directly on the thermostat.

4. The unit should not be positioned di-

rectly above any obstructions.

5. The condensate drain should have suf-

ficient fall (1” per 10’) in any horizontal

run between Cassette and drain. Maxi-

mum condensate pump lift is 36”.

6. There should be a minimum 1” clear-

ance above the depth of the Cassette

and the false ceiling for proper instal-

lation, shown below (see the “CAC Di-

mensions” section in the back of this

IOM for cabinet sizing):

Small Cabinet Dimension A = 12¾” min.

Medium Cabinet Dimension A = 11½” min.

Large Cabinet Dimension A = 13½” min.

Dimension A + 1” = minimum space

above the false ceiling for installation

A

A +1”

Figure #1

Model #

Evaporator

Condenser

Btuh

Factory Installed

Piston-Orifice Size

Field Changeover

Piston-Orifice Size

CACA24

T2CA4400

T2CA2400

T2CA8400

.059”

.063”

CACA24

T3CA9240

T3CA2240

T3CA9940

.059”

.063”

* “4” in the capacity decoding field = 24,000 Btuh

Evaporator

Importent - Replace the existing

piston (

before installing the unit)

with the piston supplied in the Kit Bag:

when a CACA24 evaporator is matched with a

T2CA4400, T2CA2400, T2CA8400 or T3CA9240, T3CA2240,

T3CA9940 condenser which has a 24,000 Btuh compressor

(“4” in the capacity decoding field) the piston will need relacement

only on the 24,000 Btuh zone. *

Your EMI evaporator unit contains the appropriate piston for your model. Refer to

this document to determine if a change is required based on your condenser rating. If

your match is

not listed below no piston change is required. (See chart)

PISTON/ORIFICE INSTALLATION INSTRUCTION