CAC Cassette Evaporator

CAC CASSETTE CHASSIS POSITIONING AND INSTALLATION

Ceiling opening:

• (In existing construction) Remove enough

ceiling panels to provide clearance space

for mounting unit to ceiling joists.

• Before beginning the installation, inspect

the unit location, test the strength of the

ceiling joists to insure they will support

the weight of the unit.

• Determine mounting method:

- On wooden beams use threaded

rods, washers, and nuts to suspend

support brackets.

- With metal structures, secure thread-

ed rods on an existing angle or install

a new support angle.

- On newly built concrete slabs secure

threaded rods with inserts and em-

bedded bolts.

- For previously built concrete slabs install

hanging bolts with an expansion anchor.

- Follow local building codes for required

safety cables, braces, etc.

Cabinet

A

B

Small

19½”

23”

Medium

29⅝”

31½”

Large

29⅝”

43

11

16

A template for ceiling cut-out and rod posi-

tions can be found with the Cassette unit.

An opening in the false ceiling will have to

be cut to the following sizes:

Small cabinet 23¼” x 23¼”

Medium cabinet 33⅞” x 33⅞”

Large cabinet 46 x 33⅞”

NOTE: Make sure the ceiling grid is

supported separately from the Cas-

sette. The ceiling must not be sup-

ported by any part of the Cassette

unit, fascia or any associated wiring

or pipe work.

Figure #2

1. Use the template (provided) to cut the

ceiling opening and determining the

rod positions.

2.000 X 45° TYP

Rod

Positions

1.500 TYP

Rod

Positions

MOUNTING THE CAC CASSETTE

CEILING EVAPORATOR

ELECTROMECHANICAL

THERMOSTAT

An optional thermostat can be obtained

through EMI or your local distributor. In

addition to positioning the Cassette cor-

rectly, it is very important to locate the wall

mounted thermostat in the optimum posi-

tion to ensure good temperature control.

Therefore the installation should be se-

lected with the following points in mind:

1. Position the thermostat approximately

5 ft. above floor level.

2. Avoid external walls and drafts from

windows and doors.

3. Avoid positioning near shelves and cur-

tains as these restrict air movement.

4. Avoid heat sources (direct sunlight,

heaters, dimmer switches, etc.)

5. Seal wiring holes in the wall behind

the thermostat to avoid drafts.