ProSYS Version 7.XX - Supplementary Instructions

Bus Zone Parameters: iWISE DT AM Grade 3

Quick Keys Parameter

Default

Range

[2][0][3][zz]
[4]

Automatic Microwave Bypass

No

Defines whether the MW channel will be bypassed or not while the
detector identifies trouble in the MW channel.

[2][0][3][zz]
[4][1] to [2]

Automatic Microwave Bypass Options

1) No - While detecting a problem in the MW channel it is not
bypassed. Alarm condition cannot be established until the MW
channel is fixed.
2) Yes - Switches the detector to operate only in PIR mode in case of
MW trouble.

[2][0][3][zz]
[5]

Green Line

Yes

A feature that follows environmental guidelines by avoiding surplus
emission. This feature defines the activation of the microwave
channel while the system is disarmed.

[2][0][3][zz]
[5] [1] to [2]

Green Line Options

1) No - Green Line feature is disabled. MW is constantly activated.
2) Yes – Green Line feature is enabled.

[2][0][3][zz]
[6]

Anti-Mask

Enable

Defines the operation of Anti Masking detection.

[2][0][3][zz]
[6] [1] to [2]

Anti-Mask Options

1) Disable 2) Enabled and behaves according to the settings defined
in quick keys [2][0][3][zz][7] .

[2][0][3][zz]
[7]

Arm/Disarm

No

Defines the operation of the anti masking feature while the detector
is armed or disarmed.

[2][0][3][zz]
[7] [1]

Arm/Disarm Options

1) No – When detector is armed or disarmed Anti-mask behaves
according to the settings defined in quick keys [2][0][3][zz][6]
2) Yes –When detector is armed Anti-mask is disabled. When
detector is disarmed Anti-mask behaves according to the settings
defined in quick keys [2][0][3][zz][6]

[2][0][3][zz]
[8]

Self Test

Remote

Used to test the detection technologies. In the event of a failed test, a
Self Test Trouble is created.