Retrotec DucTester 341 User Manual

Page 12

Advertising
background image

Page 12 of 83
©Retrotec Inc. 2014

Program/Region

Units/Test

Pressure

Leakage requirement

2012 IECC International
Energy Conservation
Code

Global

CFM

25

/100 sq ft at

+ or - 25 Pa

Post Construction Test:
Total Duct Leakage: <= 4 CFM

25

/100 sq ft conditioned floor area.

OR
Rough-in Test with air handler
Total Duct Leakage: <= 4 CFM

25

/100 sq ft

OR
Rough-in Test with no air handler:
Total Duct Leakage: <= 3 CFM

25

/100 sq ft


Required:
-Where ducts are located outside the conditioned space
-In existing houses where more than 50% of the ducts are replaced

Not Required:
- If all ducts are located in the conditioned space

New York State Energy
Code
NY: USA

CFM

25

/100 sq ft

Total leakage at
±25 Pa

Total Duct Leakage: <= 8.0 CFM

25

/100 sq ft of conditioned floor area or 6% of air

handler flow. Measured at supply closest to air handler.
Test equipment must be certified by manufacturer that it complies with ASTM
E1554-07 and ASHRAE Standard 152. Duct leakage to outdoors acceptable
under Method A of ASMT E1554-07.

North Carolina Energy
Conservation Code
NC: USA

CFM

25

/100 sq ft

Total leakage at
– 25 Pa

Total Duct Leakage: <= 6.0 CFM

25

/100 sq ft of conditioned floor area.

Depressurize to -25 Pa measured at supply closest to air handler.
Test equipment must be certified by manufacturer that it complies with ASTM
E1554-07.

Northwest ENERGY STAR
Homes
ID, MO, OR, WA: USA

CFM

50

/sq ft

CFM

50

+ 50 Pa

Total Duct Leakage, air handler in un-conditioned space
CFM

50

<= floor area (sq ft) X 0.04 (which is same as CFM

50

/ sq ft <= 0.04)

OR CFM

50

<= 50 (when house < 1250 sq ft)

OR
Total Duct Leakage, air handler in conditioned space
CFM

50

<= floor area (sq ft) X 0.06 (which is same as CFM

50

/ sq ft <= 0.06)

OR CFM

50

= 75 (when house < 1250 sq ft)


Not Required:
If both the ducts and air handler are located within the conditioned space

Oregon State Energy
Code
OR: USA

Washington State Energy
Code
WA: USA

CFM

25

/sq ft

Total leakage at
+ 25 Pa

Total Duct Leakage
with air handler NOT installed <= floor area (sq ft) X 0.04 CFM

25

with air handler installed <= floor area (sq ft) X 0.08 CFM

25

OR
Duct Leakage to Outdoors (recommended where possible)
<= floor area (sq ft) X 0.06 CFM

25