©Retrotec Inc. 2014

Average Operating

Pressure (Pa)

Multiplier for

CFM25

45

1.42

50

1.52

55

1.60

60

1.69

65

1.77

70

1.85

75

1.93

80

2.01

85

2.08

90

2.16

95

2.23

100

2.30

105

2.37

110

2.43

115

2.50

120

2.56

125

2.63

130

2.69

135

2.75

140

2.81

145

2.87

150

2.93

155

2.99

160

3.05

165

3.10

170

3.16

175

3.21

180

3.27

185

3.32

190

3.38

195

3.43

200

3.48

When possible, use actual operating conditions to determine the best multiplier to use from the table
above.

Calculate a loss factor for supply and return leaks

Supply Loss Factor = (SLS x SLP x SPM)

Where: SLS is Supply Leakage Split (default 0.5)

SLP is Supply Leakage Penalty (default 1.0)

SPM is Supply Pressure Multiplier (default 1.0)

Supply Loss Factor

= 0.5 * 1.0 * 1.0

= 0.5

Advertising