Retrotec DucTester 341 User Manual

Page 40

Advertising
background image

Page 40 of 83
©Retrotec Inc. 2014

Duct Leakage to Outdoors may be measured using only one gauge to alternatively measure the house to
outdoor pressure then the duct to outdoor pressure, until the house and ducts are at the same pressure
with respect to the outdoors. The method requires connecting and disconnecting the blue tube,
alternately measuring the house and duct pressure and adjusting the fans separately until the house and
ducts are at the same pressure.

When the house and ducts are at the same pressure, “Flow” on the DucTester gauge displays the result
for Duct Leakage to Outdoors.

For depressurization, set the Blower Door to pull air out of the building and the DucTester to pull air out
of the duct system. If your standard requires 50 Pa, substitute 50 for 25.

Figure 32: 1 Gauge Duct Leakage to Outdoors under depressurization, setting the building pressure

24. Ensure that the Device is “340” and the correct DucTester Range is selected on the gauge.
25. Close all doors and windows and shut off any exhaust fans in the building.
26. Connect the blue tube from the duct register to the gauge, run the red tube from the gauge to the

outdoors, and run the yellow and green
tubes to the DucTester.

27. Manually adjust the DucTester speed (with

the Speed Control Knob on the DucTester)
to reach -25 Pa in the ducts. Wait 60
seconds.

28. With the DucTester still running,

disconnect the blue tube from the gauge
so the blue port on the gauge is open to
the house.

29. Manually adjust the Blower Door speed

(with the Speed Control Knob on the Blower Door fan) to change
the building pressure until -25 Pa appears for Duct Pressure (Channel A) of the gauge.

30. With the Blower Door still running, connect the blue tube to the gauge and re-adjust the DucTester

speed to again set the duct pressure to -25 Pa.

31. Record duct leakage, “Flow” on the gauge, when you’re confident the building and duct pressures

have both been stabilized at -25Pa.

Figure 33: 1 Gauge Duct Leakage to Outdoors under
depressurization, setting the duct pressure

Advertising