SDC / DHC

Operation

EN2H-0220GE51 R0308

25

At outside temperatures below the frost-protection limit (see
4.2.3 "System Parameters" menu, pg. 51) the

heating circuits are

controlled as follows:

Without wall devices: Based on a lowered room temperature

specification of 3 °C.

With wall devices: Based on the room frost-protection limit of

the respective heating circuit of 10 °C (see "Direct Heating
Circuit" or "Mixed Heating Circuit 1", "Mixed heating circuit 2"
menu, parameter 08 = room frost-protection limit).

An active holiday program can be cancelled in case of early
return.

► Press

button.

► Turn input button

î

and switch to automatic mode.

The active holiday program has been cancelled.

Current date

Current date... (current date + 250 days)

An active holiday program appears in the basic display with
information on the return date.

Pos: 21 /156-Honeywell/Bedienung/Taste_Anlageninformation @ 1\mod_1207644494728_6.doc @ 9450

Control during

holidays

Cancellation

Factory setting

Setting range