Honeywell SDC User Manual

Page 34

Advertising
background image

Operation

SDC / DHC

34 EN2H-0220GE51

R0308

4.2.2 "Timeprograms"

menu

Individualised switching time programs for heating and hot-water
operation can be created in this menu. Here, the factory-set
default programs P1 (and, if enabled, P2 and P3 as well) of each
heating circuit and the hot-water circuit are overwritten by
individualised switching times and temperature specifications.
This is especially advantageous if correspondingly adapted
heating programs are to be created in case of periodically
recurring assignments with different assignment times (e.g. shift
work). Max. three heating cycles, each with a switch-on and
switch-off time, are available for each day of the week for
programming switching times. Each heating cycle can also be
combined with a freely-selectable temperature specification.

The default programs are not lost when overwritten by individually
created programs. Individualised programs, however, are deleted
when default programs are reloaded and must be recreated. For
this reason, individualised switch-on / switch-off times and
temperature specifications should always be entered in the tables
provided for this purpose (see 5 Log, pg. 60).

Press

button.

Returning to the basic display takes place by pressing the

button or automatically after the set information time (see
4.1.2.7 "System information" button, pg. 26).