Honeywell SDC User Manual

Page 54

Advertising
background image

Operation

SDC / DHC

54 EN2H-0220GE51

R0308

4.2.3.3.3 Individualised

operating mode for each heating circuit

Each heating circuit can be assigned an individualised operating
mode.

► Press

button.

► Select desired heating circuit (HC, MC-1 or MC-2) by turning

the input button

î

.

► Confirm selected circuit by pressing the input button

î

.

► Select flashing operating mode by turning the input button

î

.

► Confirm set operating mode by pressing the

button or the

input button

î

.

► With short-term operating modes (ABSENT, PARTY), set

desired target value by turning the input button

î

and confirm

set value by pressing the input button

î

.

Alternative: Automatic acceptance of the value after the set
information time (see 4.1.2.7 "System information" button, pg. 26).

Pos: 50 /156-Honeywell/Bedienung/Sommer_Heizgrenze @ 1\m od_1207647058244_6.doc @ 9900

4.2.3.4 Summer / Heating limit

This parameter specifies the end of heating operation depending
on the outside temperature based on the following criteria:

Quick increase in outside temperature

If the averaged outside temperature is below the set value and
the current outside temperature is 2 K above the set value,
heating operation is interrupted.

Slow increase in outside temperature

Deactivation is also initiated when the averaged and current
outside temperature exceeds the set value.

Setting

C