Safety instructions

SDC / DHC

8 EN2H-0220GE51

R0308

2.2.1 Power

supply

Do not disconnect the controller from the mains supply!

The battery for saving all individualised data is otherwise
unnecessarily strained. The frost-protection function of the
controller is deactivated.

2.2.2 Connection

conditions

All electrical connection work may only be carried out by qualified
personnel!

2.2.3 Cable

cross-sections

1.5 mm

2

for all cables carrying 230 V (power supply, burner,

pumps, actuator).

0.6 mm

2

for bus cables (recommended type J-Y(St)Y 2 x 0.6)

0.5 mm

2

for sensors, selectors and analog signal cables.

2.2.4 Maximum

cable

lengths

Sensor, selector and analog inputs

We recommend using cables no longer than 200 m. Longer
connection lines could be used, but increase the risk of
interference.

Relay outputs

Unlimited cable length.

Bus connections

Max. length of 100 m from the first bus subscriber to the last one
(incl. wall modules).

2.2.5 Cable

installation

Install cables for sensors apart from the cables carrying 230 V!
Branch boxes in the sensor cable must be avoided!