Operation

EN2H-0220GE51 R0308

37

The switch-off time cannot be set higher than the switch-on time
of a subsequent cycle.

If the switch-on time is changed, the corresponding time bar
display is adjusted to the right-hand side.

If the switch-off time is made equal to the switch-on time, the
corresponding cycle is deleted. A subsequent cycle is
automatically shifted to the position of the deleted cycle upon
acceptance.

With subsequent insertion of a cycle that has been bumped up,
the corresponding day of the week must be reprogrammed.

A flashing switch-off time is accepted by pressing the input button

î

.

Pos: 35 /156-Honeywell/Bedienung/Zyklustemperatur @ 1\mod_1207645359213_6.doc @ 9645

4.2.2.4.3 Cycle

temperature

Once the switch-off time is accepted, the associated cycle
temperature appears flashing and can be changed immediately
with the input button

î

. With heating circuits, the displayed cycle

temperature is always based on the desired room temperature;
with the hot-water circuit, it is based on the desired normal hot-
water temperature in the selected cycle.

A flashing cycle temperature is accepted by pressing the input
button

î

.

At the same time, the last called-up cycle appears flashing so that
it may be monitored; additional cycles can then be selected
directly and edited in the same way in the order: switch-on time,
switch-off time, cycle temperature.