SOLID STATE ECONOMIZER SYSTEM

63-2484—2

12

Fig. 16. Mounting the W7212 module on sheet metal.

C7400 Enthalpy Sensor and C7650A

Temperature Sensor Location and Mounting

Outdoor air sensing: Mount the C7400 Enthalpy Sensor or

C7650A Temperature Sensor in any orientation where it is

exposed to freely circulating air but protected from rain, snow

and direct sunlight.

Return air sensing: For differential enthalpy or temperature

control, a second C7400 Enthalpy Sensor or C7650A

Temperature Sensor is connected to the W7459 or W7212.

Mount the second sensor in the return air duct as far as

possible from the outdoor air sensor.

Wiring

CAUTION

Can Cause Electrical Shock or Equipment Damage.

Disconnect power supply before connecting wiring.

Disconnect the power supply before connecting wiring to

prevent electrical shock or equipment damage. All wiring must

comply with applicable local codes, ordinances and

regulations.

OPERATION AND CHECKOUT

C7046C (Discharge) and C7150B (Mixed) Air Sensors

The C7046C discharge air sensor is applied following the coils

in the supply air to the conditioned space. The C7150B mixed

air sensor is mounted in the mixing box, where the “best”

combination of outdoor and return air temperature can be

measured. Use either a discharge or a mixed air sensor to

provide input to the economizer module through T and T1

Terminals.

Fig. 17. C7046C and C7150B Air Temperature Sensors

resistance versus temperature.

C7400A Solid State Enthalpy Sensor

The C7400A Solid State Enthalpy Sensor is used with a solid

state economizer control and damper actuator to proportion an

outdoor air damper in a ventilation system.

Figure 18 is a partial psychometric chart with single C7400A

Sensor and W7459A Economizer Logic Module performance

curves. The curves illustrate the reset in the temperature

control point due to changes in relative humidity.

The enthalpy control setpoint A,B,C or D combines

temperature and humidity conditions, resulting in the control

curve shown in Fig. 18. When the enthalpy or outdoor air is

below (left of) the appropriate curve, the outdoor air damper

can proportion open on a call for cooling. If outdoor air enthalpy

rises above (to the right of) the control curve, the outdoor air

damper closes to the minimum position.

For differential enthalpy, turn the control setpoint to D (fully

clockwise). If outdoor air enthalpy is lower than return air enthalpy,

the outdoor air damper proportions open on a call for cooling.

If outdoor air is higher enthalpy than return air enthalpy, the

outdoor air damper closes to minimum position. Differential

enthalpy control provides energy savings and increased

comfort by using the air with the lowest enthalpy.

If outdoor air enthalpy and return air enthalpy are equal, the

outdoor air damper proportions open on a call for cooling.

The relationship between the C7400A Sensor output current

and relative humidity is shown in Fig. 19.

C7650A Solid State Temperature Sensor

The C7650A Solid State Temperature Sensor is used with a

solid state economizer control and damper actuator to

proportion an outdoor air damper in a ventilation system.

When outdoor air temperature is higher than return air

temperature, the outdoor air damper closes to the minimum

position. When the outdoor air temperature and the return air

temperature are equal, the outdoor air damper proportions

open on a call for cooling.

The relationship between the C7650A Sensor output current

and the air temperature is shown in Fig. 20.

M20601

4500

4000

3500

3000

2500

2000

1500

1000

55

60

65

70

75

80

85

90

95

100

15

20

25

30

35

RESIST

ANCE (OHMS)

TEMPERATURE (DEGREES)

M9099

F

C

3,000 OHMS AT

77F (25C)