Honeywell M8405 User Manual

Solid state economizer system, Application, Features

Advertising
background image

PRODUCT DATA

63-2484-2

Solid State Economizer System

(CONSISTING OF: C7046C DISCHARGE AIR SENSOR OR C7150B MIXED AIR SENSOR, C7400A

SOLID STATE ENTHALPY SENSOR OR C7650A SOLID STATE TEMPERATURE SENSOR, M7415

OR M8405 DAMPER ACTUATORS OR MODULATING DIRECT COUPLED ACTUATORS (MS7505),

T6031H THERMOSTAT AND W7459 OR W7212 SOLID STATE ECONOMIZER LOGIC MODULE)

APPLICATION

The Solid State Economizer System provides an economical

method of providing cooling air by incorporating outdoor air in

the first stage of cooling in heating, ventilating and air

conditioning (HVAC) systems. The Solid State Economizer

System consists of the C7046C Discharge Air Sensor or

C7150B Mixed Air Sensor, C7400A Solid State Enthalpy

Sensor or C7650A Solid State Temperature Sensor, M7415

or M8405 Damper Actuators or Modulating Direct Coupled

Actuators (MS7505), T6031H Thermostat and W7212 or

W7459A,C Solid State Economizer Logic Module.

FEATURES

C7046C Discharge Air Sensors have probe lengths of 8 in.

(203 mm) and nominal sensor resistance of 3000 ohms at

77°F (25°C).

• No setting or calibration required.
• Solid state components not affected by dust or dirt.
• Fast reacting.
• Rugged aluminum insertion probe.
C7150B Mixed Air Sensor is used with the W7212/W7459

Economizer Module to sense mixed or discharged air in roof-

top packaged air conditioning equipment.

• No setting or calibration required.
C7400A Solid State Enthalpy Sensor and C7650A Solid State

Temperature Sensors are used with the W7212/W7459 Solid

State Economizer Logic Module to sense outdoor and return

air enthalpy or temperature.

• C7400A senses and combines temperature and

humidity (enthalpy) of outdoor air (heat index).

• C7650A senses temperature only.
• When enthalpy/temperature of outdoor air increases,

the outdoor air damper closes to a preset minimum

position.

• When enthalpy/temperature of outdoor air is low, the

outdoor air damper opens to reduce the building

cooling load.

• Additional economizer savings are achieved when two

C7400A Solid State Enthalpy Sensors are connected to

one Logic Module for differential enthalpy changeover

control.

C7150B

M7415/M8405

C7046C

W7459A,C

C7400A/C7650A

W7212

T6031H

Contents

Application ........................................................................

1

Features ...........................................................................

1

Ordering Information ........................................................

2

Specifications ...................................................................

3

Specifications: M7215 ......................................................

4

Specifications: W7212A Logic Module .............................

6

Installation: M7215, M7415, M8405 .................................

7

Wiring: M7215, M7415, M8405 ........................................

8

Operation and Checkout .................................................. 12

Settings and Adjustments ................................................. 14

Sequence of Operation .................................................... 16

Operation: W7212 ............................................................ 17

Settings and Adjustments: W7212 ................................... 18

Checkout and Troubleshooting ........................................ 19

Checkout and Troubleshooting: W7212 ........................... 31

Advertising
This manual is related to the following products: