SOLID STATE ECONOMIZER SYSTEM

15

63-2484—2

M7415 and M8405 Damper Actuators

Adjusting Minimum Position (Ventilation)

The M7415 Damper Actuator is adjusted for desired minimum

position using a Q709 Actuator Mounted Minimum Position

Potentiometer and/or a remote S963B1136 Manual

Potentiometer. The M8405 Damper Actuator has an integral

thumbwheel for minimum position adjustment.

M7415 Minimum Position Adjustment

1. Run actuator to fully closed position and disconnect 24

Vac from terminals TR and TR1.

2. Connect minimum position potentiometer to terminals P

and P1 (T and T1 are disconnected).

3. Reconnect 24 Vac to terminals TR and TR1 and adjust

the potentiometer for the desired minimum position.

4. When the Q709 Actuator Mounted Minimum Position

Potentiometer is used and a remote potentiometer is not

connected in series, jumper terminals P and P1 on the

Q709A.

M8405 Minimum Position Adjustment

1. Connect the 24 Vac to the actuator at terminals T and X

(D is not connected).

2. Adjust the thumbwheel on the actuator for desired

minimum position.

Discharge Air Temperature Setpoint

Adjustment—M7415 Only

This temperature range can be adjusted either up or down by

wiring a resistor in series (to increase the setpoint) or in parallel

(to decrease the setpoint) with the C7150B, depending on the

application. See Fig. 21 and 22 for explanation.

Fig. 21. Increasing C7150B setpoint.

Fig. 22. Decreasing C7150B setpoint.

W7459A,C Solid State Economizer Logic

Module

Two potentiometers with small screwdriver slots for adjustment

are located on the face of the module.

Minimum Position Adjustment

W7459A ECONOMIZER LOGIC MODULE

1. Make sure the factory-installed jumper is in place

across terminals P and P1 (terminals T and T1 are

disconnected.

2. Connect 24 Vac at terminals TR and TR1 and adjust the

potentiometer on the face of the W7459A with a small

screwdriver for desired minimum position.

W7459C ECONOMIZER LOGIC MODULE

1. Connect 24 Vac at terminals TR and X (D is not connected).

2. Adjust thumbwheel on motor for desired minimum position.

Enthalpy Changeover Setpoint

Single enthalpy: the enthalpy changeover setpoint is set to

return the outdoor air damper to the minimum position when

the enthalpy rises above its setpoint. The enthalpy setpoint

scale markings, located on the W7459, are A, B, C, D; see Fig.

18 for the corresponding control point. The factory-installed

620-ohm jumper must be in place across terminals + and S

R

.

Fig. 23. Location of enthalpy setpoint potentiometer,

minimum position potentiometer and LED.

Differential Enthalpy Changeover Setting

(USE THIS OPTION ONLY WITH TWO-STAGE COOLING
THERMOSTATS.)
Differential enthalpy control uses two C7400 Enthalpy Sensors

or two C7650A Temperature Sensors connected to one W7459

Solid State Economizer Logic Module.

T

USE 1%, 1/8 W OR HIGHER RESISTOR

M1544C

T1

M7415

C7150

R

RESISTOR VALUE (OHMS)

681

2760

3650

4420

4750

4870

NO RESISTOR

C7150B SETPOINT °F (°C)

54.5—61.5 (12.5—16.4)

68.4—80.1 (20.3—26.8)

87.4—110.3 (30.8—45.5)

104.7—150 (40.4—65.5)

116—194 (46.7—90)

120—300 (49—149)

50—56 (10—13.3)

T

USE 1%, 1/8 W OR HIGHER RESISTOR

M1545C

T1

M7415

C7150

R

RESISTOR VALUE (OHMS)

18.2K

24K

30K

NO RESISTOR

C7150B SETPOINT °F (°C)

36—44 (2.2—6.7)

39.5—47 (4.0—8.3)

42—49 (5.6—9.4)

50—56 (10—13.3)

1

1

M9098B

ENTHALPY

CHANGEOVER

SETPOINT

MINIMUM

DAMPER

POSITION

SETTING

LED LIGHTS

WHEN OUTDOOR

AIR IS SUITABLE

FOR FREE COOLING

MINIMUM DAMPER POSITION ADJUSTMENT

IS PRESENT ONLY ON W7459A,D MODELS.