SOLID STATE ECONOMIZER SYSTEM

63-2484—2

26

Fig. 33. W7212A used in two-stage cooling system with Honeywell Series 72 Actuator and time clock for occupancy.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA

LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED

BY A 24 VAC INPUT.

FOR T7300 ONLY

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE

REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO

SR AND SR+ FOR DIFFERENTIAL ENTHALPY.

M24220

1

2

3

4

2

6

7

USE THE FOLLOWING CONTACTS INSTEAD OF TIMER

FOR T7300, USE A1 AND A2 TERMINALS.

FOR T7350 USE AUX TERMINAL.

FOR TB7220 OR TB8220 USE A TERMINAL

THE TERMINALS ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE.

EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.

SEE WIRING DIAGRAMS FOR T7350 AND TB7220/TB8220.

TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE THERMOSTAT.

UNOCCUPIED

ST6008

TIMER

L1

(HOT)

L2

FDR

FDR

FAN

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENT

TERMINAL STRIP

T7300 OR T874

THERMOSTAT

1

C

G

W1

Y1

R

W2

RC

RH

G

X

W1

Y1

Y2

W2

OCCUPIED

4

6

COOL 2

Y2

FAN

DELAY

RELAY

W

R

T6031 AMBIENT

LOCKOUT

CONTROL

50 F SETPOINT

N1

P1

T1

SR

SO

AQ

EF1

4

EF

3

5

2

1

TR

MINIMUM POSITION

ADJUSTMENT

P

T

AQ1

SO+

SR+

TR1

24 Vac

COM

24

Vac

HOT

+

2K

3

1K

1S

1S1

5

7

620 OHM

RESISTOR

W7212

C7150B MIXED

AIR OR C7046A

DISCHARGE

AIR SENSOR

+

0/2-10 VDC

INDOOR AIR

SENSOR

N

EXHAUST

FAN

L1

(HOT)

L2

S

+

C7400

OUTDOOR

AIR

ENTHALPY

SENSOR

F

1
2
3
4
5

+

~

MS7XXX

HONEYWELL

ACTUATOR

8

9

9

8

5