SOLID STATE ECONOMIZER SYSTEM

17

63-2484—2

OPERATION: W7212

The purpose of the economizer is to use outdoor air for

cooling, whenever possible, to reduce compressor operation.

Power at the N terminal determines the Occupied/Unoccupied

setting:

— W7212:

• 24 Vac (Occupied).
• No power (Unoccupied).

— W7213,W7214:

• W7213 (CHANGEOVER TERMINAL B)

— 24V power to B: System is in heating mode.

— No power to B: System is in cooling mode.

• W7214 (CHANGEOVER TERMINAL O)

— 24V power to O: System is in cooling mode.

— No power to O: System is in heating mode.

NOTE: When module is operating in Occupied mode, the

minimum position is defined by the potentiometer.

When the module is operating in Unoccupied mode,

and there is no call for cooling, the damper drives fully

closed.

When wired as shown in Fig. 28–33, the logic module

responds to the cooling thermostat signal. The system uses

C7400 Solid State Enthalpy Changeover Sensor(s) or C7650

Dry Bulb Temperature Sensor(s). The C7400 responds to both

dry bulb temperature and humidity, allowing use of outdoor air

at higher temperatures for free cooling when humidity is low.

The C7650 responds only to dry bulb temperature; use only in

dry, arid climates.

The logic module functions as a true first stage of cooling

providing maximum energy economy during the cooling cycle.

It automatically locks out free cooling during heating; holding

the outdoor air damper at the minimum position setting.

The logic module can operate as either a basic free cooling

controller, or it can incorporate additional functions. Table 5

details the input/output (I/O) logic of the module.

Fig. 24. S963B1128 Remote Potentiometer used with logic

module for remote damper control.

a

For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.

b

Power at N terminal determines Occupied/Unoccupied setting:

• W7212: 24 Vac (Occupied), no power (Unoccupied).

• W7213,W7214: No power (Occupied), 24 Vac (Unoccupied).

c

Modulation is based on the mixed air sensor signal.

d

Modulation is based on the DCV signal.

e

Modulation is based on the greater of DCV and mixed air sensor signals, between minimum position and either maximum posi-

tion (DCV) or fully open (mixed air signal).

f

Modulation is based on the greater of DCV and mixed air sensor signals, between closed and either maximum position (DCV) or

fully open (mixed air signal).

M20603A

P1

P

ECONOMIZER

R

MINIMUM

POSITION

ADJUSTMENT

W

B

CW

CLOSE

S963B1128 REMOTE

POTENTIOMETER

CW

Table 5. W7212 Economizer I/O Logic.

INPUTS

OUTPUTS

Demand Control

Ventilation (DCV)

Enthalpy

a

Y1

Y2

Compressor

N Terminal

b

Outdoor

Return

Stage 1 Stage 2

Occupied

b

Unoccupied

b

Damper

Below set (DCV

LED Off)

High (Free

Cooling LED Off)

Low

On

On

On

On

Minimum position

Closed

On

Off

On

Off

Off

Off

Off

Off

Low (Free

Cooling LED On)

High

On

On

On

Off

Modulating

c

(between

min. position and full-

open)

Modulating

c

(between

closed and full-open)

On

Off

Off

Off

Off

Off

Off

Off

Minimum position

Closed

Above set (DCV

LED On)

High (Free

Cooling LED Off)

Low

On

On

On

On

Modulating

d

(between

min. position and DCV

maximum)

Modulating

d

(between

closed and DCV

maximum)

On

Off

On

Off

Off

Off

Off

Off

Low (Free

Cooling LED On)

High

On

On

On

Off

Modulating

e

Modulating

f

On

Off

Off

Off

Off

Off

Off

Off