SOLID STATE ECONOMIZER SYSTEM

21

63-2484—2

Fig. 28. W7459A/C7400 used in two-stage cooling system with single enthalpy changeover and with M7415 Actuator.

L1

(HOT)

L2

FDR

FDR

FAN

FAN

DELAY

RELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENT

TERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

MOTOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR

IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.

WITH T7300, USE CONTACTS A1 AND A2 INSTEAD OF S7005 TIMER.

M10115A

T7300 OR T874

THERMOSTAT

T1

P1

P1

P

T1

1

3

4

2

5

2K

S

1

1

2

3

4

6

TR

TR1

SO

SR

+

+

TR

M7415 ACTUATOR

W7459A ECONOMIZER PACKAGE

+

C

G

W1

Y1

R

W2

RC

G

X

W1

Y1

Y2

W2

C7400

OUTDOOR

AIR

ENTHALPY

SENSOR

UNOCCUPIED

OCCUPIED

ST6008

TIMER

3

2

5

1K

COOL 2

Y2

4

5

T

6

7

7

8

8

P

T

1S

1S1

MINIMUM POSITION

ADJUSTMENT

TR1

MINIMUM

POSITION

MIXED

AIR

SENSOR

24 VAC

C7150B MIXED

AIR OR

C7046A

DISCHARGE

AIR SENSOR

M7415

TR

TR1

T1

P1
P

24 VAC

SENSOR

MIN

POS

T

620 OHM

RESISTOR

W

R

T6031 AMBIENT

LOCKOUT

CONTROL

50 F SETPOINT

RH