Solid state economizer system – Honeywell M8405 User Manual

Page 23

Advertising
background image

SOLID STATE ECONOMIZER SYSTEM

23

63-2484—2

Fig. 30. W7212 used with M7215 Damper Motor and T7350 Thermostat.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

THE SAME TRANSFORMER CAN BE USED FOR THE THERMOSTAT AND ACTUATOR.

IF SEPARATE HEATING AND COOLING TRANSFORMERS ARE USED, REMOVE JUMPER AT THERMOSTAT.

T7350 - TERMINAL “AUX” IS POWERED BY THE HEATING TRANSFORMER (RH).

IF POWERING THE ECONOMIZER TERMINAL “N” WITH THE THERMOSTAT TERMINAL “AUX”, BE SURE THE ECONOMIZER IS POWERED BY THE

SAME TRANSFORMER AS TERMINAL “AUX”. IF NOT, USE AN ISOLATION RELAY TO POWER “N”.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE

WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.

EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.

M13657

S

1

2

3

2

+

4

5

C7400

OUTDOOR

AIR

ENTHALPY

SENSOR

L1

(HOT)

L2

FAN

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENT

TERMINAL STRIP

T7350

THERMOSTAT

1

C

G

W1

A2

Y1

Y2

R

W2

RC

RH

G

X

W1

Y1

Y2

W2

AUX

COOL 2

N1

P1

T1

SR

SO

AQ

EF1

EXHAUST

FAN

L1

(HOT)

L2

4

EF

3

5

2

1

TR

MINIMUM POSITION

ADJUSTMENT

P

T

AQ1

SO+

SR+

TR1

24 Vac

COM

24 VAC COM

24

Vac

HOT

2-10 VDC CONTROL

+

4

620 OHM

RESISTOR

C7150B MIXED

AIR OR C7046A

DISCHARGE

AIR SENSOR

+

0/2-10 VDC

INDOOR AIR

SENSOR

N

24 VAC HOT

SIGNAL INPUT

W7212

M7215

5

3

Advertising
This manual is related to the following products: