Checkout and troubleshooting: w7212, Caution – Honeywell M8405 User Manual

Page 31

Advertising
background image

SOLID STATE ECONOMIZER SYSTEM

31

63-2484—2

CHECKOUT AND TROUBLESHOOTING:

W7212

Checkout requires a 9V battery, 620 ohm, 1.2K ohm, 5.6K

ohm, and 6.8K ohm resistors. Use Table 10 and Fig. 36 for

checkout.

CAUTION

Equipment Damage Hazard.

Excessive force can damage potentiometer

controls.

Use a small screwdriver when adjusting enthalpy

changeover and minimum damper position controls.

Fig. 36. Meter location for checkout and troubleshooting

(W7212 shown).

M20612

N1

P1

T1

N

2V

2V

2V

B

A

SR

SO

AQ

C

D

Free

Cool

10V

EXH

DCV

EXH

Set

10V

DCV

Max

10V

DCV

Set

Min

Pos

Open

P

T

AQ1

SO+

SR+

1

2

DC VOLTMETER

620 OHM RESISTOR

W7212

+

S

+

C7400

1

2

INSERT DC VOLTMETER BETWEEN AQ AND AQ1 FOR

CHECKOUT AND TROUBLESHOOTING.

JUMPER USED FOR SINGLE ENTHALPY CONTROL.

Table 10. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator.

Step

Checkout Procedure

Proper Response

1.

CHECKOUT PREPARATION
Disconnect power at TR and TR1.

All LED are off; Exhaust Fan contacts are open.

Disconnect devices at P and P1.
Jumper P to P1.
Place 5.6K ohm resistor across T and T1.
Jumper TR to 1.
W7212 only: Jumper TR to N.
If connected, remove C7400 Enthalpy Sensor from

terminals S

O

and +.

Connect 1.2K ohm 4074EJM Checkout Resistor across

terminals S

O

and +.

Put 620 ohm resistor across S

R

and +.

Set minimum position, DCV setpoint, and Exhaust

potentiometers fully CCW.
Turn DCV maximum position potentiometer fully CW.
Set enthalpy potentiometer to D.
Apply power (24 Vac) to terminals TR and TR1.

2.

DIFFERENTIAL ENTHALPY
Execute step one, Checkout Preparation.

Place 620 ohm resistor across S

O

and +.

Place 1.2K ohm resistor across S

R

and +.

Free cool LED turns on.

Remove 620 ohm resistor from S

O

and +.

Free cool LED turns off.

3.

SINGLE ENTHALPY
Execute step one, Checkout Preparation.

Set enthalpy potentiometer to A (fully CCW).

Free cool LED turns on.

Set enthalpy potentiometer to D (fully CW).

Free cool LED turns off.