SOLID STATE ECONOMIZER SYSTEM

63-2484—2

20

Fig. 27. M8405A Damper Actuator used in two-stage cooling system with differential enthalpy changeover and W7459C

Economizer.

L1

(HOT)

L2

M8405

T

D

APPLY

24VAC T-X

FOR MIN POSN

T-D FOR

MAX POSN

FDR

FDR

FAN

FAN

DELAY

RELAY

HEAT 1

HEAT 2

COOL 1

COOL 2

HVAC EQUIPMENT

TERMINAL STRIP

W

R

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

MOTOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR

IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.

M3865B

T7300 OR T874

THERMOSTAT

X

D

D

6

X

1

3

4

5

2

2K

S

C7400

OUTDOOR

SENSOR

1

1

2

3

4

TR

TR1

SO

SR

+

+

T

M8405 ACTUATOR

W7459C ECONOMIZER PACKAGE

+

C

G

W1

Y1

Y2

R

W2

W

R

S

C7400

RETURN

SENSOR

+

RC

G

X

W1

Y1

Y2

W2

RH

T675/T6031 MIXED

AIR CONTROL

55¡ F SETPOINT

T6031 AMBIENT

LOCKOUT CONTROL

50¡ F SETPOINT

UNOCCUPIED

OCCUPIED

ST6008

TIMER

3

2

5

1K

4

5

6

6

MAX

SW

SET

MIN

X