T6031h thermostat – Honeywell M8405 User Manual

Page 5

Advertising
background image

SOLID STATE ECONOMIZER SYSTEM

5

63-2484—2

Shaft: Single-ended drive shaft with crank arm supplied.

Reliability:

Full-Stroke Cycles: 60,000. Repositions: 1,500,000.

Approvals:

Underwriters Laboratory Inc.: Flammability Rating: UL94-5V.

Component Recognized: File No. E4436, Guide No.

XAPX2, Vol. 9, Section 1, 7-25-83.

Fig. 4. M7215, M7415A, and M8405A Damper Motor dimensions in in. (mm).

a

Timing with 60 Hz power.

b

Spring return.

c

Modulating.

d

Three-position with field adjustable minimum position control.

e

Mounts directly on damper shaft.

T6031H Thermostat

A standard spdt switch, without a case, that acts as a

changeover thermostat.

Electrical Rating:

0.25A at 1/.4V to 12 Vdc inductive load.

Control Range, Element Temperature and Differential:

See Table 2.

Approval:

Underwriters Laboratories Inc. Listed:

File E4436, Vol. 4, Guide No. XAPX2.

Dimensions:

See Fig. 5.

Table 1. M7415A/M7405A Actuator Specifications.

Power (Vac)

Torque

Model Number

Voltage (Vac)

50/60 Hz

(Drive) (Hold)

Timing

(sec)

a

Stroke

(°)

(lb-in.)

(Nm)

Open Rotation

(Shaft End View)

Spring Return

(Shaft End View)

M7415A

b,c

24

8

5

90

90

25

2.8

ccw

cw

M8405A

b,d

24

7

3

90

90

25

2.8

ccw

cw

M7415B

b,c

24

8

5

90

90

25

2.8

cw

ccw

M7215A

b,c

24

8

5

90

90

25

2.8

ccw

cw

MS7505

a,b,c,e

24

13

5

90

90

44

5

cw/ccw

cw/ccw

7/16

(11)

1-1/4

(32)

5-3/16 (132)

4-1/2 (114)

3-1/2 (89)

2-1/4 (57)

4-1/2

(114)

5

(127)

4-1/32

(102)

1-3/8 (35)

3-1/8 (79)

M3851

TOP VIEW

SIDE VIEW

POWER END VIEW

1/4 (6)

4-1/2

(114)

Advertising