Settings and adjustments: w7212, Demand control ventilation setpoint, Adjusting minimum and maximum positions – Honeywell M8405 User Manual

Page 18: Caution, Minimum position adjustment

Advertising
background image

SOLID STATE ECONOMIZER SYSTEM

63-2484—2

18

NOTES:

DCV and Free Cooling have setpoints and LED indications.

For models with a B terminal (W7213):

No power to B: cooling mode, free cool enabled. Module follows logic detailed above.

24V power to B: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).

For models with an O terminal (W7214):

24V power to O: cooling mode, free cool enabled. Module follows logic detailed above.

No power to O: heating mode, free cool disabled. Actuator drives to minimum position (closed when Unoccupied).

SETTINGS AND ADJUSTMENTS: W7212

CAUTION

Equipment Damage Hazard.

Excessive force can damage potentiometer

controls.

Use a small screwdriver when adjusting enthalpy

changeover and minimum damper position controls.

Potentiometers with small screwdriver adjustment slots,

located on device face, provide adjustments for several

parameters (see Fig. 25 for locations on device):

— DCV setpoint.

— Minimum damper position.

— DCV maximum damper position.

— Enthalpy changeover.

— Exhaust setpoint.

Fig. 25. Potentiometer and LED locations (W7212 shown).

Demand Control Ventilation Setpoint

The logic module modulates the outdoor damper to provide

ventilation based on the 0/2-10 Vdc DCV. With no cooling

signal, the DCV overrides the outdoor air damper when

ventilation requires additional outdoor air.

Adjusting Minimum and Maximum Positions

The minimum position potentiometer maintains the minimum

outdoor air flow into the building during the occupied period.

The minimum position allows for the building effluents. The

DCV maximum position potentiometer allows the installer to

limit the amount of outdoor air flow into the building when the

DCV overrides the mixed air sensor and allows the proper

ventilation based on occupancy. Setting the DCV maximum

position of the damper prevents the introduction of large

amounts of hot or cold air into the space by preventing the

dampers from opening 100%. Set the DCV maximum position

at the maximum design occupancy.

IMPORTANT

With the DCV maximum position set below the mini-

mum position, the minimum position overrides the

maximum position (negating most DCV functions of

the logic module, as the damper cannot move).

NOTES:

When the mixed air sensor takes control based on

an increased requirement for cooling, it overrides

the DCV maximum position potentiometer and can

drive the damper full-open.

If the mixed air temperature drops to 45°F, the

mixed air sensor overrides the DCV and fully

closes the damper to protect from freezing the hot

or chilled water coils. Control returns to normal

once the mixed air temperature rises to 48°F.

Minimum Position Adjustment

For detailed assistance in minimum position selection

reference the Economizer Application Guide (form 63-8594)

Ventilation section. The following provides basic guidelines for

minimum position selection and adjustment:

IMPORTANT

• Adjust the minimum position potentiometer to allow

the minimum amount of outdoor air for building efflu-

ents, as required by local codes, to enter the building.

• This procedure requires use of a quality thermometer

capable of reading to 0.5°F (0.25°C).

NOTE: Make minimum position adjustments with at least a

10°F (6°C) temperature difference between outdoor

and return air.

1. Calculate the appropriate mixed air temperature. See

Equation 1.

2. Disconnect mixed air sensor from terminals T and T1.

3. Place a jumper across terminals T and T1.

4. Ensure that either the factory-installed jumper is in place

across terminals P and P1 or, if remote damper position

is required, that it is wired according to Fig. 24 and

turned fully clockwise.

5. Connect 24 Vac across terminals TR and TR1.

6. Carefully adjust the potentiometer on the face of the

device with a small screwdriver until the mixed air tem-

perature reaches the calculated value.

NOTE: Ensure that the sensed air is well-mixed.

DEMAND CONTROL

VENTILAION SETPOINT

ENTHALPY

CHANGEOVER SETPOINT

LED LIGHTS WHEN

DEMAND CONTROL

VENTILAION INPUT

IS ABOVE SETPOINT

EXHAUST

FAN SETPOINT

LED LIGHTS

WHEN EXHAUST

CONTACT IS MADE

MINIMUM DAMPER

POSITION SETTING

M20604

N1

P1

T1

N

2V

2V

2V

B

A

SR

SO

AQ

C

D

Free

Cool

10V

EXH

DCV

EXH

Set

10V

DCV

Max

10V

DCV

Set

Min

Pos

Open

P

T

AQ1

SO+

SR+

MAXIMUM DAMPER

DEMAND CONTROL

VENTILATION SETPOINT

LED LIGHTS WHEN

OUTDOOR AIR IS

SUITABLE FOR

FREE COOLING

Advertising