SOLID STATE ECONOMIZER SYSTEM

9

63-2484—2

To mount the C7046C Sensor in a junction box (see Fig. 11):

1. Cut a 1/2 in. (13 mm) hole in the duct or plenum surface

at the desired location.

2. Remove the center rear knockout from the junction box

and insert the sensor probe through the knockout with

the flange flat against the junction box.

3. Using the flange as a template, mark and drill two holes

in the junction box and the duct or plenum surface for no.

8 mounting screws.

4. Insert the sensor probe through both the junction box

knockout and the 1/2 in. (13 mm) hole drilled in the duct

or plenum and fasten the junction box and sensor to the

duct or plenum surface with the two no. 8 sheet metal

screws (not provided).

Fig. 10. Mounting C7046C Air Temperature Sensor on duct

or plenum.

Fig. 11. Mounting C7046C Discharge Air Temperature Sensor in junction box.

Wiring

CAUTION

Can Cause Electrical Shock or Equipment Damage.

Disconnect the power supply before connecting the

wiring.

Make sure wiring complies with applicable local codes,

ordinances and regulations.

Connect low voltage wiring from the sensor to the appropriate

system component terminals using solderless connectors as

shown in Fig. 10 and 11.

SCREWS NOT PROVIDED.

1

SENSOR PROBE

SYSTEM DUCT OR PLENUM

FLANGE

NO. 8

MOUNTING

SCREWS (2)

TO APPROPRIATE

SYSTEM COMPONENTS

(SEE WIRING DIAGRAM)

SENSOR WIRES WITH

2 SOLDERLESS

CONNECTORS

1

M9086

SCREWS NOT PROVIDED.

1

1

SENSOR PROBE

SYSTEM DUCT OR PLENUM

FLANGE

STANDARD 2 X 4 (51 X 102)

OUTLET BOX (OPTIONAL)

CONNECTOR

AND

LOCKNUT

BLANK

FACEPLATE

(OPTIONAL)

TO APPROPRIATE

SYSTEM COMPONENTS

(SEE WIRING DIAGRAM)

SENSOR WIRES WITH 2

SOLDERLESS CONNECTORS

M9088