Enthalpy changeover setpoint, Exhaust setpoint, Checkout and troubleshooting – Honeywell M8405 User Manual

Page 19: Dcv maximum position adjustment, Differential enthalpy changeover setting

Advertising
background image

SOLID STATE ECONOMIZER SYSTEM

19

63-2484—2

7. If all minimum and maximum position adjustments are

complete, remove the T-T1 jumper and reconnect the

mixed air sensor.

EQUATION 1. FORMULA TO AID MINIMUM POSITION ADJUSTMENT.

(T

O

× OA)+(T

R

× RA)= T

M

Where:

T

O

= Outdoor air temperature

OA = Percent of outdoor air

T

R

= Return air temperature

RA = Percent of return air

T

M

= Resulting mixed air temperature

NOTE: The following sample calculation uses only Fahren-

heit temperature.

EXAMPLE: Assume local codes require 10% outdoor air dur-

ing occupied conditions, outdoor air is 60°F and

return air is 75°F. Under these conditions, what is

the temperature of the mixed air?

(0.1 × 60°F)+(0.9 × 75°F)=6.0°F + 67.5°F=73.5°F

Mixed air will be 73.5°F when OA is 60°F and RA is 75°F with

10 percent outdoor air entering the building.

DCV Maximum Position Adjustment

1. Disconnect mixed air sensor from terminals T and T1

and short terminals T and T1.

2. Connect a jumper between terminals AQ and AQ1.

3. Connect 24 Vac across terminals TR and TR1.

4. Adjust the potentiometer on the face of the device with a

small screwdriver for desired maximum position.

5. If all minimum and maximum position adjustments are

complete, remove the T-T1 jumper and reconnect the

mixed air sensor.

Enthalpy Changeover Setpoint

Outdoor Enthalpy Changeover Setpoint
(Single Enthalpy)

The outdoor enthalpy changeover setpoint returns the outdoor

air damper to minimum position when enthalpy rises above its

setpoint. Enthalpy setpoint scale markings, located in the

device, are A, B, C and D. See Fig. 18 for the corresponding

control point. The factory-installed 620-ohm jumper must be in

place across terminals SR and SR+. Temperature and humidity

points to the left of the selected curve will allow the dampers to

open for free cooling.

Differential Enthalpy Changeover Setting

Differential enthalpy control uses two C7400 Enthalpy Sensors

connected to one logic module. The logic module compares

outdoor air to return air.

NOTE: Turn the enthalpy setpoint potentiometer fully clock-

wise to the D setting.

The logic module selects the lower enthalpy air (return or

outdoor) for cooling. For example, when outdoor air has lower

enthalpy than return air, the module calls to open the outdoor

air damper to bring in outdoor air for free cooling.

Exhaust Setpoint

The exhaust setpoint determines when the exhaust fan runs

based on damper position. When the exhaust fan call is made,

the module provides a 60 ±30 second delay before exhaust fan

activation. This delay allows the damper to reach the

appropriate position to avoid unnecessary fan overload.

NOTES:

EF and EF1 are 24V dry contacts only. An external

line voltage contactor is required to operate the

exhaust fan.

When the exhaust fan is deactivated the EF and

EF1 contacts open immediately.

CHECKOUT AND TROUBLESHOOTING

Tables 6 through 10 provide step-by-step economizer checkout

and troubleshooting steps. See Fig. 23 and 25 for enthalpy

setpoint potentiometer, minimum position potentiometer and

LED locations.

Fig. 26. Meter location for checkout and troubleshooting.

1

1

2

2

M9097

ENTHALPY CHANGEOVER

SETPOINT

LED LIGHTS WHEN

OUTDOOR AIR IS SUITABLE

FOR FREE COOLING

INSERT DC MILLIAMMETER BETWEEN SO AND S FOR CHECKOUT

AND TROUBLESHOOTING.

JUMPER USED FOR SINGLE ENTHALPY CONTROL.

TR

TR1

A

B

C

D

SO

SR

+

+

+

C7400

620 OHM

JUMPER

DC

MILLIAMMETER

W7459

S

+