SOLID STATE ECONOMIZER SYSTEM

63-2484—2

10

IMPORTANT

Failure to follow these wiring practices can introduce

electrical interference (noise) that can cause erratic

system operation:

a. Keep wiring at least one foot away from large induc-

tive loads such as motors, line starters, lighting bal-

lasts, and large power distribution panels.

b. Shielded cable is required in installations where

these guidelines cannot be met.

c. Ground shield only to grounded controller case.

d. Make good physical wiring connections to ensure

good electrical connections.

e. Make sure that building earth ground connections

are not intermittent or missing.

f. Mount sensor only in recommended environment.

MS7505 Damper Actuators

Location and Mounting

LOCATION
Locate the actuator as close as possible to the equipment to

be controlled. Refer to Fig. 12 for mounting dimensions.

Wiring

Disconnect power supply before connecting wiring to prevent

electrical shock or equipment damage. All wiring must comply

with applicable local codes and ordinances.

Fig. 12. MS7505 Dimensions Diagram.

Dimensions, Approximate 9.72 in. high x 3.94 in. wide x 2.95

in. deep (247 mm high x 100 mm wide x 75 mm deep)

Fail Safe Mode Spring Return

Electrical Connections Enclosed screw terminal strip (22 to

14 AWG) (Enclosed screw terminal strip [0.324 to 2.08 sq

mm])

Frequency 60 Hz

Manual operation Manual Crank

Spring Return Direction By orientation

Rotational Stroke 95 ±3 degrees

Rotational Stroke Adjustment Mechanically limited 5 degree

increments

Shaft Adapter Type Self-centering clamping

Compatible Damper Shafts 3/8 to 1.06 round or 3/8 to 11/16

square (10 to 27 round or 10 to 18 square)

Mounting Direct Coupled

External Auxiliary Switches Available Yes

Rated Torque (44 lb-in. (5 Nm)

Maximum Stall Torque 75 lb-in. (8.5 Nm)

Spring Return Torque 44 lb-in. (5 Nm)

Maximum Noise Rating, Holding (dBA @ 1m) 20 (no audi-

ble noise)

Maximum Noise Rating, Driving (dBA @ 1m) 40

Environmental Rating NEMA2

Ambient Temperature Range -40°F to +140°F (-40°C to

+60°C)

Storage Temperature Range -40°F to +158°F (-40°C to

+70°C)

Operating Humidity Range (% RH) 5 to 95% RH, non-con-

densing

Materials Aluminum housing, Plenum rated plastic access

cover

Weight 6 lb (2.72 kg)

Approvals:

CE:

89/336/ECC, 73/23/EEC

C-Tick N314

Canadian Underwriters Laboratories, Inc. cUL C22.2 No.

24-93

Underwriters Laboratories, Inc. UL873, Plenum Rated

Includes Mounting Bracket, Self-Centering Shaft Adapter,

3mm crank

T6031H THERMOSTAT

Location and Mounting

The T6031H Thermostat mounts either vertically or horizontally

on a wall or panel. Locate the remote bulb as far from the

controller as capillary tubing allows.

Mounting Sensing Elements

T6031H: Install the bulb in the return airflow where air of

average temperature can circulate around it.

IMPORTANT

Do not overtighten clamps to the point of distorting

the sensor bulb because overtightening causes a sig-

nificant shift in bulb calibration.

Mounting Thermostat

Mount the thermostat using the back mounting plate as shown

in Fig. 5.

9-3/4

(247)

1-9/16

(40)

2-1/2

(64)

MIN.

3 (76)

MIN.

3 (76)

MIN.

FROM

SHAFT

END

6-1/8

(156)

1-9/16

(40)

1-9/16

(40)

3-15/16 (100)

2-15/16 (75)

1/4 (6)

M20952