Framing and clearances, Warning – Heat & Glo Fireplace BRAVO 704-902 User Manual

Page 7

Advertising
background image

Heat & Glo • Bravo • 704-902 Rev. F • 10/08

7

Figure 3.1 Appliance Locations

A

B

C

D

E

Inches

45-1/8

34-3/8

63-7/8

25-1/4

No maximum

Millimeters

1146

873

1622

641

A

½

½

A

B

C

B

E

B

D

In addition to these framing dimensions, also reference the following sections:

• Clearances and Mantel Projections (Section 3.C and 3.D)

• Vent Clearances and Framing (Section 6).

Note: These dimensions
are for fl ush wall fi nishing
method. For a recessed
arch fi nishing method refer
to Option B in Finishing
(Section 11).

3

3

Framing and Clearances

Note:
Illustrations reflect typical installations and are FOR

DESIGN PURPOSES ONLY.

Illustrations/diagrams are not drawn to scale.

Actual installation may vary due to individual design

preference.

Fire Risk

Provide adequate clearance:

• Around air openings

• To combustibles

• For service access

Locate appliance away from traffi c areas.

A. Selecting Appliance Location

When selecting a location for your appliance it is important to
consider the required clearances to walls (see fi gure 3.1).

Note: For actual appliance dimensions refer to Section 16.

WARNING