4.11 Function Code 17 (11h) - Report HC900 ID

Description

Function code 17 (11h) is used to report the device information such as Slave ID, device description and
firmware version.

Query

The query message specifies the function code only.

Example: Read Device ID from a slave at address 2.

Query message format for function code 17 (11h)

Slave Address (00 for

TCP)

Function

Code

CRC (RTU)

CRC (RTU)

TCP Example

00

11

RTU Example

02

11

CRC

CRC

Response

The response is a record format describing the instrument.

Response message format for function code 17 (11h)

Slave

Address

Function

Code

Byte

Count

Slave

ID

Run

Indicator

Status

Device

Description

Model

ID

Device

Class

ID

Device

Mapping

CRC

(RTU)

CRC

(RTU)

Slave Address – 00 for TCP. RTU is slave address. Example: 02

Slave ID - The Slave ID number for the HC930 is 93 (hex). For the HC950 it is 95 (hex) (one byte) (byte
3). For HC970 it is 70 (hex). For HC970R it is 7A (hex).

Run Indicator Status - (one byte) (byte 4). 00=OFF; FF=ON

Device Description - (bytes 5-20)- 16 Character ASCII Message with the following format:

‘H’ ‘C’ ‘9’ ‘5’

or

‘3’

or

‘7’

‘0’

or

‘A’

‘’ ‘‘ up to 9 character version number in

floating point notation.

zeros are appended for

the remaining bytes

For example, an HC950 with version number 2.000 would have the following device description:

‘H’ ‘C’ ‘9’ ‘5’ ‘0’ ‘’ ‘‘ ‘2’ ‘.’ ‘0’ ‘0’ ‘0’ 0 0 0 0

Model ID - 00 (one byte) (byte 21)

Device Class ID - The Device Classification. (one byte) (byte 22)

Class ID

Class

00

Generic Class (Fixed Address Mappable)

01-FF Future

Continued