54

HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

6.5 Analog Input - Function Code 03

Summary

Not available for versions 4.0 and later. Used to access analog input parameters for the first 8 channels of
the first 8 modules of Rack #1. (Address compatible with UMC800.)

To access any analog input channels use Function Code 04. See page 32.

Analog Input Example: AI1 through AI64. The mapping is with respect to card position starting with the
first card module position and continuing to the 8

th

module position. The first module position would be

AI1 thru AI8. The next AI card in slot 2 would be AI9 thru AI16 and so on.

Function Code Support:

Reads – Function Codes 03 (limited to the first 8 slots of Rack #1)

Table 6-4 Analog Input Value Addresses - Function Code 03

Fixed
Address
(hex)

Fixed
Register
(decimal)

Channel Number

Access

Notes

1800

6145

Analog Input #1

R

1802

6147

Analog Input #2

R

1804

6149

Analog Input #3

R

1806

6151

Analog Input #4

R

1808

6153

Analog Input #5

R

180A

6155

Analog Input #6

R

180C

6157

Analog Input #7

R

180E

6159

Analog Input #8

R

1810

6161

Analog Input #9

R

1812

6163

Analog Input #10

R

1814

6165

Analog Input #11

R

1816

6167

Analog Input #12

R

: : :

187E

6271

Analog Input #64

R

Floating Point
in Engineering
Units.

Example

Read Analog Inputs 1 and 2 from HC900 at slave address 01 using Function Code 03.

TCP:

00 03 18 00 00 04

RTU:

01 06 00 FA 00 01

CRC

CRC

Response from HC900 where AI1 = 100.0 and AI 2 = 55.32

TCP:

00 03 08 42 C8 00 00 42 5D 47 AE

RTU:

01 03 08 42 C8 00 00 42 5D 47 AE

CRC

CRC