90

HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

6.16 Device Control

Summary

This table contains addresses for the Device Control group #1.

See the Device Control Register Maps in Table 6-1 for starting and ending addresses (hex) for Device
Control #2 through Device Control #16 Map Addresses
.

The Modbus Device Control number address for a Device Control can also be obtained from the Hybrid
Control Designer report.

Function Code Support:

Reads – Function Code 3

Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )

Writes – Function Code 6 for presetting an integer value

For custom addresses view or print a report in HC Designer.

Table 6-26 Device Control parameters

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter Name

Access Notes

6B00

27393

Reset Request

W

Unsigned 16 Integer
Data Ignored

6B01

27394

Status Indicator

R

Bit Packed
Bits 0 – 6: Device Control State
Bit 0: Ready: 0=NO, 1=YES
Bit 1: Prestart: 0=NO, 1=YES
Bit 2: Starting: 0=NO, 1=YES
Bit 3: Running: 0=NO, 1=YES
Bit 4: Stopping: 0=NO, 1=YES
Bit 5: Disabled: 0=NO, 1=YES
Bit 6: Failed: 0=NO, 1=YES
Bit 7: Run Request Input State; 0=OFF, 1=ON
Bit 8: Device Feedback Started; 0=NO, 1=YES
Bit 9: Device Failed; 0=NO, 1=YES
Bit 10: Automatic Reset; 0=Manual, 1=Auto
Bit 11-15: Unused

6B02 27395 Remaining

Delay

Time

R

Floating Point in Seconds

6B04

27397

Start Delay

R/W

Floating Point in Seconds

6B06

27399

Stop Delay

R/W

Floating Point in Seconds

6B08

27401

Feedback Fail Delay

R/W

Floating Point in Seconds