HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

6.12 Stage

Summary

This section contains addresses for the Stage function blocks.

See the Stage Register Maps in Table 6-1 for starting and ending addresses (hex) for Stage #1 through
Stage #8 Map Addresses
.

The Modbus Stage number address for a Stage block can also be obtained from the Hybrid Control Designer
report.

Function Code Support:

Reads – Function Code 3

Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point)

Writes – Function Code 6 for presetting an integer value

For custom addresses view or print a report in HC Designer.

Table 6-22 Stage Parameters

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter Name

Access Notes

6200

25089

PV1

R

Floating Point in Engineering Units

6202

25091

PV2

R

Floating Point in Engineering Units

6204 25093 Stage

#1-4

Override Status

R Bit

Packed:

Bit 0: Stage #1 Override Active: 0=NO, 1=YES

Bit 1: Stage #1 Override ON: 0=OFF, 1=ON

Bit 2: Stage #2 Override Active: 0=NO, 1=YES

Bit 3: Stage #2 Override ON: 0=OFF, 1=ON

Bit 4: Stage #3 Override Active: 0=NO, 1=YES

Bit 5: Stage #3 Override ON: 0=OFF, 1=ON

Bit 6: Stage #4 Override Active: 0=NO, 1=YES

Bit 7: Stage #4 Override ON: 0=OFF, 1=ON

Bits 8-15: Unused

6205

25094

Stage #1-4 PV
On/Off Comparison

R Bit

Packed:

Bit 0: Stage #1 On Comparitor: 0=PV1, 1=PV2

Bit 1: Stage #1 Off Comparitor: 0=PV1, 1=PV2

Bit 2: Stage #2 On Comparitor: 0=PV1, 1=PV2

Bit 3: Stage #2 Off Comparitor: 0=PV1, 1=PV2

Bit 4: Stage #3 On Comparitor: 0=PV1, 1=PV2

Bit 5: Stage #3 Off Comparitor: 0=PV1, 1=PV2

Bit 6: Stage #4 On Comparitor: 0=PV1, 1=PV2

Bit 7: Stage #4 Off Comparitor: 0=PV1, 1=PV2

Bit 8-15: Unused