HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

6.15 Alternator

Summary

This section contains addresses for the Alternator #1group.

See the Alternator Register Maps in Table 6-1 for starting and ending addresses (hex) for Alternator #2
through Alternator #16 Map Addresses
.

The Modbus Alternator number address for an Alternator can also be obtained from the Hybrid Control
Designer report.

Function Code Support:

Reads – Function Code 3

Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )

Writes – Function Code 6 for presetting an integer value

ATTENTION

Output Order Sequence registers must be written in a single transaction. Duplicate sequence values (1-16)
are not permitted.

For custom addresses view or print a report in HC Designer.

Table 6-25 Alternator Parameters

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter Name

Access Notes

6700

26369

Alternator Status

R

Bit Packed
Bit 0: Enable: 0=NO, 1=YES
Bit 1: Low Capacity
0=Meeting Capacity, 1=Low Capacity
Bit 2-15: Unused

6701

26370

Device Ready (#1-16) R

Bit Packed:
Bit 0: Device #1 Ready: 0=NO, 1=YES
Bit 1: Device #2 Ready: 0=NO, 1=YES
Bit 2: Device #3 Ready: 0=NO, 1=YES
Bit 3: Device #4 Ready: 0=NO, 1=YES
Bit 4: Device #5 Ready: 0=NO, 1=YES
Bit 5: Device #6 Ready: 0=NO, 1=YES
Bit 6: Device #7 Ready: 0=NO, 1=YES
Bit 7: Device #8 Ready: 0=NO, 1=YES
Bit 8: Device #9 Ready: 0=NO, 1=YES
Bit 9: Device #10 Ready: 0=NO, 1=YES
Bit 10: Device #11 Ready: 0=NO, 1=YES
Bit 11: Device #12 Ready: 0=NO, 1=YES
Bit 12: Device #13 Ready: 0=NO, 1=YES
Bit 13: Device #14 Ready: 0=NO, 1=YES
Bit 14: Device #15 Ready: 0=NO, 1=YES
Bit 15: device #16 Ready: 0=NO, 1=YES