HC900 Hybrid Controller Communications User Guide

49

12/07

6.4 Loop Values

About loop addresses

This table contains fixed addresses of Loop #1. See Table 6-1 for starting and ending fixed addresses
(hex) for Loop #2 through Loop #32
. Each successive control loop is offset by 256 with the exception
that loop 25 has a new starting address and loop 26 – 32 are offset by 256. The loop number corresponds to
the PID block entry sequence during Hybrid Control Designer configuration. The Modbus loop number
address for a loop can also be obtained from the Hybrid Control Designer printout of Block Modbus
Addresses.

The addresses given in Table 6-3 do not necessarily apply to loops in the custom map. For custom
addresses view or print a report in HC Designer.

Function Code Support:

Reads – Function Code 3

Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )

Writes – Function Code 6 for presetting an integer value

Table 6-3 Loop Values

Loop type

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter Name

PIDOn

/
Off

Carb3Pos AMB

Access Notes

0040

0065 PV

9 9 9

9

R

Floating Point in Engineering Units.

0042

0067

Remote Set Point;
SP2

9 9 9

R/W

Floating Point in Engineering Units.
When the remote setpoint source is configured as
LSP2, the value can be written.

0044

0069

Working Set Point

9 9 9

R/W

Floating Point in Engineering Units.
On a write to this register the instrument will update
the proper set point according to the loop’s currently
selected set point.

0046

0071 Output

9 9 9

9

R/W

Floating Point in Engineering Units.

0048

0073

PV

9 9 9

9

R

Floating Point in Engineering Units.

004A

0075

Carbon Potential block
temperature

9

R

Floating Point in Engineering Units

004C

0077

Gain #1 (Prop Band #1
if active
)

9

9

R/W

Floating Point . (in units per what was configured in
the HC900: Gain or Proportional Band)

004E

0079 Direction

9 9 9

R

Floating Point
0.0=Direct; 1.0=Reverse

0050

0081

Reset #1

9

9

R/W

Floating Point in Repeats/Minute or
Minutes/Repeat.

0052

0083

Rate #1

9

9

R/W

Floating Point in Minutes

0054

0085

Cycle Time for Analog
Scan

9 9 9

9

R

Floating Point in Seconds

0056

0087

PV Low Range

9 9 9

9

R

Floating Point in Engineering Units.

0058

0089

PV High Range

9 9 9

9

R

Floating Point in Engineering Units.

005A

0091

Alarm #1 SP #1

9 9 9

9

R/W

Floating Point in Engineering Units.

005C

0093

Alarm #1 SP #2

9 9 9

9

R/W

Floating Point in Engineering Units.

0060

0097

Gain #2 (Prop Band #2
if active
)

9

9 R/W

Floating

Point