Honeywell HC900 User Manual

Page 59

Advertising
background image

Revision 10

HC900 Hybrid Controller Communications User Guide

51

12/07

Loop type

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter Name

PIDOn

/
Off

Carb3Pos AMB

Access Notes

00FB

0252

Set Point State

9 9 9 9

R/W

Bit Packed (selects either SP1 or SP2 as a local SP
if the HC900 is configured as such in PID setup)
Bit 0: 0:SP1; 1:SP2
Bit 1-15: Unused

00FC

0253

Remote/Local Set
Point State

9 9 9 9

R/W

Bit

Packed

Bit 0: 0:LSP; 1:RSP
Bit 1-15: Unused

00FD

0254

Tune Set State

9

9 9

R/W

Bit Packed (selects tuning constant set)
Bit 0: 0:Tune Set #1; 1:Tune Set #2
Bit 1-15: Unused

00FE

0255

Loop Status

9 9 9 9

9

R Bit

Packed

Bit 0: Mode: 0:Manual; 1:Auto
Bit 1: Set Point: 0:SP1; 1:SP2
Bit 2: Remote/Local: 0:LSP; 1:RSP
Bit 3: Tune Set: 0:Set #1; 1:Set #2
Bit 4: IMAN: 0:Inactive; 1:Active
Bit 5: LO: 0: Inactive; 1:Active
Bit 6-15: Reserved

See Table 6-28 on page 92for additional loop parameters for custom maps only.