74

HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

6.11 Sequencer

Summary

In the fixed map each Sequencer uses three non-contiguous sections of the map:

• Sequencer parameters (Table 6-21)
• Sequencer steps (Table 6-21)
Sequencer states (Table 6-21).

In a custom map the above parameters are contiguous.

Function Code Support

Read – Function Code 3

Write – Function Code 16 (10 hex)

Sequencers 1-4 Parameter Addresses

The addresses given in Table 6-18 do not necessarily apply to sequencers in the custom map. For custom
addresses view or print a report in HC Designer.

Table 6-18 Sequencers 1-4 Parameters Fixed Addresses

Starting

Address

(Hex)

Starting

Register

(Decimal)

Ending

Address

(Hex)

Ending

Address

(Decimal)

Sequencer #1 Parameters

5AA0

23201

5AB5

23222

Sequencer #2 Parameters

5D00

23809

5D1F

23840

Sequencer #3 Parameters

5F60

24417

5F7F

24448

Sequencer #4 Parameters

A000

40961

A01F

40992

Sequencers 1-4 Step 1 Addresses

The addresses given in Table 6-19 do not necessarily apply to sequencer steps in the custom map. For
custom addresses view or print a report in HC Designer.

Table 6-19 Sequencer 1-4 Step 1 Fixed Addresses

Starting

Address

(Hex)

Starting

Register

(Decimal)

Ending

Address

(Hex)

Ending

Address

(Decimal)

Sequencer #1 Step 1 Table

5AC0

23233

5CBF

23744

Sequencer #2 Step 1 Table

5D20

23841

5F1F

24532

Sequencer #3 Step 1 Table

5F80

24449

617f

24960

Sequencer #4 Step 1 Table

A020

40993

A21F

41504

Sequencers 1-4 State Addresses

The addresses given in Table 6-20 do not necessarily apply to sequencer states in the custom map. For
custom addresses view or print a report in HC Designer.