EXCEL 500/600 INSTALLATION INSTRUCTIONS

Fig. 60. XF526 Analog Input module connections

XF523A Digital Input Module

The digital input module can process DC or AC voltage
signals. The module has 12 digital inputs. When the input
voltage reaches 5 V, the digital signal is set to a status of "1".
With a hysteresis of 2.5 V, the digital input signal must fall
below 2.5 V before a digital status of "0" is reported.

Fig. 61. Digital input hysteresis

The LED functionality of each digital input channel can be
altered via 12 internal DIP switches. In the ON position
(default), the LED will illuminate when energized (normally
open contacts). In the OFF position, the LED will illuminate
when de-energized (normally closed contacts).

Max. signal voltage from non-Honeywell voltage sources:

DC Voltage: V

max

= 40 V

AC Voltage: V

max

= 28 V /

≥ 50 Hz

Input resistance:

R

i

= 15k ohms

Fig. 62. XF523A connection examples

If the inputs are used as totalizers, Table 9 applies.

Table 9. Totalizer inputs specifications

Input

Frequency

Pulse duration

Pulse internal

Chatter time

1, 2

max. 15 Hz

min. 20 ms

min. 33 ms

max. 5 ms

3 to 12

max. 0.4 Hz

min. 1.25s

min. 1.25 s

max. 50 ms

The inputs shown in row one (Input 1 to 2) may be used as fast totalizers. In this case, the input signal characteristics of row one
are valid. If they are not used as fast totalizers, the values of row two (Inputs 3 to 12) apply to them as well.

29

EN1R-1047GE51 R0902