EXCEL 500/600 INSTALLATION INSTRUCTIONS

— Type XW569 13 in. (330 mm) long (for housings one

above the other)

CAUTION

Incorrectly inserted bus cables can destroy the
modules installed.

The internal bus begins at the first housing, containing the
power supply and computer modules, and ends at the last
housing.
The protective bus connection covers must be removed.

Fig. 5. Removal of bus connection cover

The overall internal bus length (bus cable and bus in the
housings) must not exceed 6 ft (2m).
Bus cables must be routed at least 2 in. (50 mm) away from
power cables to prevent possible inductive and capacitive
interference.

Module Locations (not XCL5010)

Each housing has four plug-in module locations.

Table 1. Internal module locations

Module

Type

Module location

CPU

XC5010C /
XC6010

1

st

housing, location 4

Power
supply

XP502

1

st

housing, location 1

AI

XF521A / XF526 any

AO

XF522A / XF527 any

DI

XF523A

any

DO

XF524A / XF529 not in the 1

st

housing

3-position
output

XF525A

not in the 1

st

module

housing

Coding the Terminal Block (not XCL5010)

The terminal block is coded with pins to prevent mixing the
module types during commissioning or servicing. Mixing the
modules can damage them.
You can code the terminal block by inserting pins into
designated location holes on the terminal block in the base.

Fig. 7. Inserting the code pin in the terminal block

Table 2 shows the coding pin positions for the individual
module types:

Table 2. Code pin position by module type

Module

Type

Pin position

CPU

XC5010C, XC6010

08

Power supply

XP502

06

AI

XF521A, XF526

07

AO

XF522A, XF527

11

DI

XF523A

09

DO

XF524A, XF529

10

3-position output XF525A

12

Fig. 6. Internal module numbering

Table 1 shows the plug-in location to which each module may
be assigned:

NOTE: Distributed I/O modules are coded differently. See

Distributed I/O Product Data (EN0B-0090GE51).

7

EN1R-1047GE51 R0902