Beacon II Controller

Programming And Reviewing Settings/Changes

The

Program Review

button is used to program, review and change all program settings for the system.

Press

“PROGRAM REVIEW”

button. The Setpoint item will appear on the LED. After a few seconds delay

the Setpoint value will display. Each time the button is pressed a different setpoint item is displayed.

Next, use the

“SELECT”

knob to change value of Setpoint Item.

Next, when the desired value is selected, press the

“ENTER”

button to place it in program memory. If the

“ENTER”

button is not pressed, the value will not be stored in the memory and thus will not be changed.

“PROGRAM REVIEW” ITEMS

A-E

Set Defrost Type (

Air

or

ELE

)

rEF

Set Refrigerant Type (R22, R404A or R507)

bot

Set Box Temperature (-30°F to +70°F)

SUP

Set Superheat (4°F to 20°F)

SLA

Set Board as a Slave (Yes or No)

dFn

Set Number of Defrosts Per Day (1, 2, 3, 4, 5, 6, 8, 10 or 12 per day)

dFF

Set Defrost Fail-safe Time (10 to 200 minutes)

dFt

Set Defrost End Temperature (40°F to 100°F)

dFS

Set Defrost Delay Start Time (0.5 Hours to 23.5 Hours)

ALH

Set Alarm High Temperature (-40°F to 90°F)

ALL

Set Alarm Low Temperature (-40°F to 90°F)

ALt

Set Alarm Time (2 to 120 minutes)

F-C

Set Fahrenheit/Celsius Temperature Units (°F / °C)