Refrigeration piping, Figure 8. drain line, Suction lines – Heatcraft Refrigeration Products II User Manual

Page 8: Suction line risers, Condensate drain lines, Figure 7. suction p-traps

Advertising
background image

8

Figure 8. Drain Line

Refrigeration Piping

Suction Lines

NOTE:

If the suction line must rise to the point higher than the suction connection on

the evaporator, a suction line trap at the outlet of the evaporator must be provided.

Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1/4’ per
10 feet for good oil return. When multiple evaporators are connected in series using a common suction line,
the branch suction lines must enter the top of the common suction line.

Suction lines that are outside of refrigerated space must be insulated. See “Line Insulation” for more
information.

Suction Line Risers

NOTE:

To provide proper oil return, a suction trap must be provided at the base of

all suction risers.

Prefabricated wrought copper traps are available, or a trap can be made by using two street ells and one
regular ell. The suction trap must be the same size as the suction line. For long vertical risers, additional
traps may be necessary. Generally, one trap is recommended for each length of pipe (approximately 20 feet)
to insure proper oil movement. See Figure 7 below for methods of constructing proper suction line P-traps.

Condensate Drain Lines

Copper drain lines should be used and properly protected from freezing. In running drain lines, provide a
minimum of 4 inches per foot pitch for proper drainage. Drain lines should be at least as large as the
evaporator drain connection. All plumbing connections should be made in accordance with local plumbing
codes. All condensate drain lines must be trapped, and run to an open drain. They must never be connected
directly to the sewer systems. Traps in the drain line must
be located in a warm ambient. We recommend a trap on all
evaporators. Traps located outside, or extensive outside
runs of drain line must be wrapped with a drain line heater.
The heater should be connected so that it is continuously
on. It is recommended that the drain line be insulated to
prevent heat loss. A heat input of 20 watts per lineal foot of
drain line for 0ºF (-18°C) room applications and 30 watts
per lineal foot for -20°F (-29°C) rooms is satisfactory.

Inspect the drain pan periodically to insure free drainage of
condensate. If the drain pan contains standing water, check
for proper installation. The drain pan should be cleaned
regularly with warm soapy water.

WARNING:

All power must be disconnected

before cleaning. The drain pan also serves as
cover for hazardous moving parts. Operation
of unit without drain pan constitutes a hazard.

NOTE:

Always trap drain lines individually

to prevent vapor migration.

Figure 7. Suction P-traps

Advertising