Beacon ii controller – Heatcraft Refrigeration Products II User Manual

Page 25

Advertising
background image

25

Beacon II Controller

System Defaults

Figure 15. Control Sensor And Piping

Table 5. System Defaults

Parameters

Code

Air

Electric

Refrigerant

rEF

R22

R404A

Box Temperature

bot

35°F

-10°F

Superheat

SUP

8°F

8°F

Slave Evaporator

SLA

No

No

No. of Defrosts Per Day

dFn

2

4

Defrost Fail-Safe Time

dFF

40 min.

30 min.

Defrost End Temperature

dFt

45°F

60°F

Defrost Delay Start Time

dFS

0 hrs.

0 hrs.

Alarm High Temperature

ALH

50°F

5°F

Alarm Low Temperature

ALL

30°F

-15°F

Alarm Time

ALt

60 min.

60 min.

Temperature Units

F-C

°F

°F