Diagnostics, Beacon ii troubleshooting guide (continued) – Heatcraft Refrigeration Products II User Manual

Page 34

Advertising
background image

34

Diagnostics

Beacon II Troubleshooting Guide (continued)

PROBLEM

Step ACTION ITEM

IF OK

IF NOT OK

E9

Multi-out to Multi-in

1.

Check for 24 volts power to the board

1. If no voltage, see “LED is not lit” above

Communication Wiring

for low voltage, see “88888 LED display”

(only shows after initial

2.

Check for crossed communication wiring

Go to

2. Correct wiring from “Master” unit Multi-out

successful connection)

(multi-out not wired to multi-in terminals)

next step

to Multi-in of “Slave” unit, etc. to all Slaves
and return to Master. (See wiring diagrams)

3.

Check for broken communication wiring

3. Correct wiring between first Slave with
error to previous board in the sequence.

(E9 continued)
Communication Error
Occurrence:

Break in the designated
lines will cause errors
as follows:

Line #

Master

Slave1

Slave 2

Slave 3

1

E9

E9

E9

E9

2

E9

no error

E9

E9

3

E9

no error

no error

E9

4

E9

no error

no error

no error

[With SMART
Controller II]

Line #

SMART

Master

Slave1

Slave 2

Slave 3

1

+COMM+

E9

no error

no error

no error

2

+COMM+

no error

E9

E9

E9

3

+COMM+

no error

no error

E9

E9

4

+COMM+

no error

no error

no error

E9

5

+COMM+

no error

no error

no error

no error

PROBLEM

Step ACTION ITEM

IF OK

IF NOT OK

88888 LED display

1.

Check Voltage to Evaporator Transformer

1. Check field wiring for breaks or shorts

(power is below 18V and

2.

Check Transformer Secondary Output Volts

Go to

2. Replace if necessary

appears at initial power)

3.

Check Voltage at Control Board (24 and C)

next step

3. Check factory wiring and connections

4.

Check Voltage at SMART Controller II

4. Check field wiring from board

1.

Check for low voltage

1. Check all steps for “88888 LED display”

LED displays

dLy

Go to

Voltage could drop off too fast to show.

then

oFF

with no

2.

Check for short in field wiring from “comp” on

next step.

2. Check internal factory wiring to

displayed errors

board to condensing unit terminal connection

compressor contactor.

3.

Replace defective contactor (holding coil)