Refrigeration piping, Figure 10, Line insulation – Heatcraft Refrigeration Products II User Manual

Page 9: Figure 9. example of pipe support

Advertising
background image

9

Figure 10.

Refrigeration Piping

1.

Normally, any straight run of tubing must be supported in at least two locations near each end of the run.
Long runs require additional supports. The refrigerant lines should be supported and fastened properly.
As a guide, 3/8 to 7/8 should be supported every 5 feet, 1-1/8 and 1-3/8 every 7 feet; and 1-5/8 and 2-1/8
every 9 to 10 feet.

2.

When changing directions in a run of tubing, no corner should be left unsupported. Supports should be
placed a maximum of 2 feet in each direction from the corner.

3.

Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in
such a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the
copper tubing.

4.

Do not use short radius ells. Short radius elbows have points of excessive stress concentration and are
subject to breakage at these points.

5.

Thoroughly inspect all piping after the equipment is in operation and add supports wherever line vibration
is significantly greater than most of the other piping. Extra supports are relatively inexpensive as
compared to refrigerant loss.

Line Insulation

After the final leak test, refrigerant lines exposed to
high or low ambient conditions should be insulated to
reduce heat loss or gain and prevent the formation of
flash gas in the liquid lines. Suction lines should be
insulated with 3/4’ wall Armstrong “Armaflex” or
equivalent. Liquid lines should also be insulated with
1/2-inch wall insulation or better. The insulation located
in outdoor environments should be protected from UV
exposure to prevent deterioration of insulating value.

Figure 9. Example of

Pipe Support

Advertising