Beacon ii controller, Status led display description, Clear / test – Heatcraft Refrigeration Products II User Manual

Page 20

Advertising
background image

20

Beacon II Controller

Programming And Reviewing Settings/Changes (continued)

Use this button to

“CLEAR/TEST”

Pressing this button ONCE will return the LED display to the default display.
With the system in the

OFF

mode, pressing and holding this button will start the

“TEST”

mode. In the

“TEST”

mode it will cycle through each output.

STATUS INDICATOR LED

A red, 3-digit, alphanumeric LED on the Beacon II board indicates status, alarms
and error codes.

Status

LED Display

Description

• OFF

Box Temp /

oFF

Box Temperature / Mode is displayed

All Evaporators

•COOLING

Single Evaporator –

Box Temp /

Coo

Box Temperature / Mode is displayed

Multiple Evaporators
Master Evap –

Box Temp /

Coo

Box Temperature / Mode is displayed

Slave Evaps –

Coo

Operating Mode is displayed

• Pumpdown

All Evaporators

Pdn

• DEFROST

All Evaporators

dEF

• TEST

All Evaporators

tSt

•SERVICE

All Evaporators

SEr

• ALARMS

A1

High Box Temp

A2

Low Box Temp

A3

System Start-Up Failure
Compressor does not start after 3 times.
(Four minutes between each try)

A4

Input Fault
Box Temp., Suction Temp., Pressure
Transducer open or not installed

CLEAR /

TEST

Advertising