Operation – Heatiator Heatilator BH60 User Manual

Page 23

Advertising
background image

23

Operation

Power Light

Indicates power to the

control board.

Status Light

Will be lit anytime there is a

call for heat.

Combustion Blower Light

Indicates Power to

combustion blower

Feed Motor Light Indicates

Power to the feed motor.

Max Temp dial

The “Max Temp Dial” is used to set the desired

maximum operating temperature of the boiler.

Feed adjuster

Sets the maximum feed rate

Test

Combustion blower, feed motor

and safety dump zone are fully

energized for the first minute.

Afterward, combustion blower

remains on low only.

Overheat Safety Zone Light

Indicates elevated boiler

water temperature. Power

flowing to Overheat circuit.

Igniter Light

Indicates power to the igniter

Lighting Mode Selector

Switched between Auto and

Manual lighting

Mode Selector/Min Temp

Dial

Used to turn the boiler on

or off and set the desired

minimum operating

temperature of the boiler.

Diagnostic Port

For diagnostic purposes only.

Requires special DDM monitor

supplied to trained technicians

exclusively.

7 Blinks: Boiler water over heat safety shut down. This re-

quires a manual reset by cycling the main power off for a few

seconds and re-connect. See explanation on page 20.

Mode Selector/Min. Temp.

Used to turn the boiler on or off and set the desired

minimum operating temperature of the boiler.

Max. Temp./ Min. Temp. Water Temperature Settings

See “Setting the boiler temperature” found on page 24.

OFF Mode

Turning the Mode Selector/Min.Temp. to OFF will shut down

the boiler.

Status light error messages:

3 Blinks: Indicates that the ESP (Exhaust Sensing Probe) has

gone out of range, too many times. May indicate axcessive

ash build-up in the exhaust stream. If the unit seems to be

operating normally, perform a manual reset by cycling the

main power off for a few seconds and re-connect.

4 Blinks: Indicates miscommunication with the aquastat, or

the sensor is not attached properly. May require a manual

reset.

5 Blinks: (In Auto Light Mode Only)

Indicates that the igniter has failed to light the fire after 40

Minutes. To reset - Turn the Mode Selector/Min. Temp. to

OFF and then back to the desired temperature.

6 Blinks : Indicates that the control has calculated poor or

incomplete combustion occurring for 25 or more minutes.

A six blink status may be set if the stove is allowed to run

out of pellets. To reset, turn Mode Selector/Min Temp dial

to “OFF” then back on to the desired temperature. If the unit

was not out of pellets, see Troubleshooting section, Page 34,

for more details.