Operation, Pellet boiler outdoor air reset operation – Heatiator Heatilator BH60 User Manual

Page 25

Advertising
background image

25

Operation

Pellet Boiler Outdoor

Air Reset Operation

w

hen the outdoor sensor is installed, at 20° F

. or below OA

T (Outdoor

Air

Temperature), the boiler will operate at the temperature set on the Maximum Temperature knob.

The boiler water temperature will decrease by 1 degree for

every 1 degree in temperature rise of the Outside

Air

.

Example 1

OA

T

w

ater

Temp

Degree Change

Max set at 185

o

65

o

140

o

-45°

Min set at 140

o

60

o

145

o

-40°

55

o

150

o

-35°

50

o

155

o

-30°

45

o

160

o

-25

o

40

o

165

o

-20

o

35

o

170

o

-15

o

30

o

175

o

-10

o

25

o

180

o

-5

o

20

o

185

o

0

o

15

o

185

o

0

o

10

o

185

o

0

o

5

o

185

o

0

o

185

o

Example 2

OA

T

w

ater

Temp

Degree Change

Max set at 180

o

65

o

150

o

*

Min set at 150

o

60

o

150

o

*

55

o

150

o

*

50

o

150

o

-30

o

45

o

155

o

-25

o

40

o

160

o

-20

o

35

o

165

o

-15

o

30

o

170

o

-10

o

25

o

175

o

-5

o

20

o

180

o

0

o

15

o

180

o

0

o

10

o

180

o

0

o

5

o

180

o

0

o

0

o

180

o

0

o

* No change in boiler temperature after reaching minimum setpoint temperature.