W8835 ENVIRAZONE PANEL

68-0258ES—04

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or

phone:

1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2. Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Input Ratings:

Voltage: 20-30 Vac, 50/60 Hz.

Power: 11 VA nominal, Class II.

Output Ratings (dampers and HVAC equipment):

1.5A run, 200,000 cycles (30 Vac) 3.5A inrush.

1.5A run, 100,000 cycles (30 Vac) 7.5A inrush.

Humidity Ratings:

90 percent RH at 95°F, non-condensing.

Temperature Ratings:

Shipping: -20 to 120°F.

Operating: -40 to 150°F.

LED:

SYSTEM mode LEDs (5) used to communicate equipment

status:

Red Heat: Heat mode.

Green Cool: Cool mode.

Yellow Purge: Purge mode.

Green Fan: Fan mode.

Red Em Heat: Emergency Heat mode.

ZONE LEDs (3) used to communicate damper status:

Green: Dampers are open or opening.

No Color: Dampers are closed or closing.

COM LED (1) used to indicate communication status:

Flashing Green: Panel is transmitting or has received data.

No color: Communications are idle.

Dimensions: 12-3/4 in. W x 10-3/4 in. H x 1-7/8 in. D.

See Fig. 1.

Finish: W8835: Taupe cover, olive-gray base.

Mounting: Mounts with four screws (provided) through holes

in cabinet back (wall anchors provided).

Wiring: Eighteen-gauge wire for all equipment and system

connections.

Wiring Connections:

EnviraCom: Four terminal strips (each with three terminals

labeled 1, 2, 3).

Dampers: Three terminal strips labeled M6 (Closed),

M4 (Open), M1 (Common).

Transformer 1: R (hot), C (Common).

Transformer 2: T1 (hot), T2 (Common).

Equipment: Rc, Rh, W1/E, W2, W3/Aux, Y1, Y2, G, O/B.

Humidifier: HUM, HUM.

Dehumidifier: DHUM, DHUM.

Ventilator: VENT, VENT.

Thermostats:

VisionPRO® IAQ TH9421 or FocusPRO THM5320C Thermo-

stats controls single- or multi-stage conventional and heat

pump equipment.

Accessories:

For required accessories, see Table 2. Optional accessories

include the W8735 Telephone Access Module for

telephone dial-in and dial-out capability, and the W8703

Damper Interface Module to control additional zones.